Operating instructions
109
This parameter determines the condi-
tions under which the set flow tempera-
ture with weather-compensated control
should be corrected by the room influ-
ence.
Valu
e
Explanation
"0" Weather-compensated control
without room influence. Set flow
temperature is not corrected.
"1" Weather-compensated control
with room influence only for
"Reduced" operating mode.
Valu
e
Explanation
"2" Weather-compensated control
with room influence only for
"Standard" operating mode.
"3" Weather-compensated control
with room influence for
"Reduced" and "Standard" oper-
ating modes.
Delivered condition 3
Setting range 0 to 3
200E Maximum set flow temperature
"Maximum flow temperature 200E"
Maximum permissible set flow tempera-
ture for a heating circuit.
The set flow temperature, which is cal-
culated from the outside temperature
and the heating curve, is limited by this
parameter to a maximum set flow tem-
perature. For the heating circuit without
mixer (A1), limited modulation properties
mean the heat pump regulates to the
return temperature. The set return tem-
perature is calculated from the set flow
temperature minus 5 K.
Note
Since the control unit only limits the set
value with this parameter, always install
an on-site temperature limiter in the flow
of an underfloor heating circuit, to restrict
the maximum temperature.
Delivered condition
400 (≙ 40 °C)
Setting range
100 to 700 (≙
10 to 70 °C)
Parameter group heating circuits/cooling circuit
200B Room temperature hook-up (heating circuits)
(cont.)
5441 603 GB
Service