Operating instructions

111
"Room temperature 7102"
With this parameter a different set room
temperature than for the heating circuits
can be specified for the separate cooling
circuit. This makes it possible, for exam-
ple, to also cool a storage room in winter,
independent of the set room tempera-
ture.
Operating instructions
Delivered condition
200 ( 20 °C)
Setting range
100 to 300 ( 10 to 30 °C)
7103 Minimum flow temperature for separate cooling circuit
"Minimum flow temperature 7103"
If a lower set flow temperature than the
value specified here results due to out-
side and room temperature according to
the cooling curve, the flow temperature
is regulated to this value.
Note
Only the set flow temperature is limited
with this value, not the actual tempera-
ture.
The minimum permissible set flow tem-
perature specified here applies both for
cooling a heating circuit as well as for
cooling a separate cooling circuit.
Delivered condition
100 ( 10 °C)
Setting range
10 to 300 ( 1 to 30 °C)
7104 Room hook-up cooling circuit
"Slope room hook-up 7104"
The influence of room temperature hook-
up can be selected, subject to a room
temperature sensor being installed.
The higher the value, the greater the
influence of the room temperature on the
set flow temperature of the cooling circuit
in weather-compensated cooling mode.
Parameter group cooling
7102 Room temperature separate cooling circuit
5441 603 GB
Service