Operating instructions

138
Parameter Code Delivered condi-
tion
Commis-
sioning
Compressor
Enable 5000 1
Output compressor stage 5030 Rated heating out-
put in accordance
with the type plate
DHW
Cylinder temperature DHW 6000
500 ( 50 °C)
DHW with e heating 6015 1
Minimum temperature 6005
100 ( 10 °C)
Maximum temperature 6006
600 ( 60 °C)
DHW hysteresis 6007
70 ( 7 K)
Booster heater hysteresis 6008
100 ( 10 K)
Start optimisation 6009 0
Stop optimisation 600A 0
Set temperature 2 600C
600 ( 60 °C)
Temperature sensor 2 600E No function
Combi cylinder 6016 No function
No. of attempts DHW 6017 1
Cylinder primary pump type 6020 3
Solar
Solar control unit type 7A00 0
Maximum temperature 7A01
1300 ( 130 °C)
Hysteresis solar pump ON 7A02
70 ( 7 K)
Hysteresis solar pump OFF 7A03
30 ( 3 K)
Flow rate 7A07 100 l/h
Detect faulty circulation 7A09 1
Electric heater
Inst. heating water heater 7900 0
Heating with electro 7902 1
Maximum stage, electric heating 7907 1
Stage at power-OFF 790A 0
Dual mode temperature, electric heating 790B
100 ( 10 °C)
Commissioning/service reports
Control parameter report
(cont.)
5441 603 GB