Operating instructions

141
Connection values of operational components
Components Connec-
tion
Connected
load [W]
Voltage [V] Max.
switching
current [A]
Primary pump/well pump 211.1 200 230 4(2)
Secondary pump 211.2 130 230 4(2)
Instantaneous heating
water heater control,
stage 1 (accessory)
211.3 10 230 4(2)
Circulation pump for cylin-
der heating (heating water
side)
211.4 130 230 4(2)
NC-Box control 211.5 10 230 4(2)
Heating circuit pump A1 212.2 100 230 4(2)
DHW circulation pump 212.3 50 230 4(2)
Solar circuit pump 212.4 130 230 4(2)
Total current max. 5(3) A
Vitocal 242-G, 400 V
Vitocal 242-G Type BWT 106 BWT 108 BWT 110
Heating output data at 5 K spread
(to EN 14511, B0/W35 °C)
Rated output kW 5.9 7.7 10.0
Cooling capacity kW 4.6 6.0 7.8
Power consumption kW 1.40 1.84 2.32
Coefficient of performance (COP)
4.2 4.2 4.3
Heating output data at 10 K
spread (to EN 255, B0/W35 °C)
Rated output kW 6.2 8.0 10.4
Cooling capacity kW 4.9 6.4 8.3
Power consumption kW 1.36 1.77 2.23
Coefficient of performance (COP),
heating
4.5 4.5 4.6
Primary circuit (brine)
Capacity l 2.8 3.1 3.4
Minimum flow rate at 5 K spread
(always maintain)
l/h 820 1120 1450
Maximum external pressure drop
(RFH) at minimum flow rate
mbar 680 630 590
Max. inlet temperature °C 25 25 25
Min. inlet temperature °C –5 –5 –5
Specification
Specification
5441 603 GB