Operating instructions

29
General information regarding the power supply
Information regarding the compres-
sor power supply
!
Please note
An incorrect phase sequence
can cause damage to the unit.
Make the compressor power
supply only in the phase
sequence specified (see termi-
nal) with a clockwise rotating
field.
If full wave soft starter is installed (see
type plate), the compressor power
fuses must have Z characteristics.
If compressor and/or instantaneous
heating water heater (accessory) are
operated at a lower tariff (power-OFF),
provide an additional cable (e.g.
NYM 3 x 1.5 mm
2
) for the power-OFF
signal from the distribution board
(meter box) to the control unit.
Information regarding the control unit
power supply
Protect the power supply to the control
unit with no more than 16 A.
For accessories and external compo-
nents which are not to be connected to
the control unit, we recommend mak-
ing the power connection to the same
fuse, but with at least the same phase
as the control unit.
Connection to the same fuse/MCB
provides additional safety when the
power is switched off. Observe the
power consumption of the consumers
connected (see page 141).
The power supply to the control unit
(3 x 1.5 mm
2
) and the cable for the
power-OFF signal can be combined in
a five-core cable. Observe the techni-
cal connection requirements of the
power supply utility.
Information regarding the power sup-
ply utility
In negotiations with your power supply
utility, different supply tariffs for the
main power circuits may be offered.
The control unit/electronics feed
must be implemented without possi-
ble blocking from the power supply util-
ity; tariffs that are subject to possible
shutdowns must not be applied to
these feeds.
The allocation of the power-OFF (for
compressor and/or instantaneous
heating water heater) is made via the
type of connection and by a setting in
the control unit (see pages 31 and
97). In Germany, the power supply
can be cut off for up to 3 x 2 hours
within any 24 h period.
Installation sequence
Power supply
(cont.)
5441 603 GB
Installation