Operating instructions

48
Calling up messages from the mes-
sage history
Messages cannot be acknowledged in
the message history.
The messages are listed in order of
occurrence with the most recent first.
Up to 30 entries are stored.
Service menu:
1. Press OK + å simultaneously for
approx. 4 s.
2. "Message history"
3. Press OK to scan information about
the required message.
Note
The service menu remains active until it
is deactivated with "Terminate serv-
ice?", or if no operation takes place for
30 minutes.
Message overview
All messages are identified by a two-digit code.
Message
System characteristics Cause Measures
02 Std after data error
Delivered condition set
after recognition of data
fault
Reconfigure system.
03 Configuration fault
System configuration
fault:
Incorrect system
scheme (contains non-
supported heating cir-
cuit)
Max. flow temperature
for heating circuit <
min. flow temperature
for cooling the heating
circuit
Cooling for unavailable
heating circuit
Check and match associ-
ated parameters, reset to
delivered condition if
required ("Reset", see
operating instructions),
and reconfigure system.
Contact your local heating
contractor if the cause of
the fault cannot be rem-
edied.
Troubleshooting
Messages
(cont.)
5441 603 GB