Message
System characteristics Cause Measures
29 Return sensor sec.
Operation with tempera-
ture value of flow temper-
ature sensor in secon-
dary circuit, minus 5 K. If
both temperature sen-
sors (secondary flow and
return) are faulty, the
heat pump stops (mes-
sage A9)
Break, secondary circuit
return temperature sen-
sor
Check resistance (Pt 500)
at plug-in connection F9
and terminals X5.10/
X5.11; replace sensor if
required.
30 Flow sensor primary
Operation with tempera-
ture value of return tem-
perature sensor in pri-
mary circuit, plus 3 K. If
both temperature sen-
sors (primary flow and
return) are faulty, the
heat pump stops (mes-
sage A9)
Short circuit, primary cir-
cuit temperature sensor,
brine inlet
Check resistance (Pt 500)
at plug-in connection F2
and terminals X5.2/X5.3;
replace sensor if
required.
31 Return sensor primary
Operation with tempera-
ture value of flow temper-
ature sensor in primary
circuit, minus 2 K. If both
temperature sensors
(primary flow and return)
are faulty, the heat pump
stops (message A9)
Short circuit, primary cir-
cuit temperature sensor,
brine outlet
Check resistance (Pt 500)
at plug-in connection F3
and terminals X5.4/X5.5;
replace sensor if
required.
38 Flow sensor primary
Operation with tempera-
ture value of return tem-
perature sensor in pri-
mary circuit, plus 3 K. If
both temperature sen-
sors (primary flow and
return) are faulty, the
heat pump stops (mes-
sage A9)
Lead break, primary flow
temperature sensor,
(brine inlet)
Check resistance (Pt 500)
at plug-in connection F2
and terminals X5.2/X5.3;
replace sensor if
required.