Operating instructions

57
Message
System characteristics Cause Measures
Check power supply,
power cable and plug to
the instantaneous heat-
ing water heater
Test instantaneous
heating water heater
control signal at con-
nections 211.3; check
high limit safety cut-out
and reset if required;
check instantaneous
heating water heater.
Installation
instructions,
instantaneous
heating water
heater
B4 A-D converter
Internal fault ADC (ana-
logue digital converter,
reference), ribbon cable
between sensor PCB
and main PCB faulty, or
PCBs faulty
Check sensor connec-
tions F1, F5, F10, F15,
F19 and F22 on the con-
troller and sensor circuit
board.
B5 EEPROM
Internal error EEPROM Replace coding card.
B9 KM BUS solar
Communication error -
KM BUS solar control
unit, or sensor S3 of
Vitosolic faulty
Check parameter
"Solar collector".
Check connection to
Vitosolic.
Check sensor S3 and
replace, if required (see
Vitosolic installation
and service instruc-
tions).
Troubleshooting
Messages
(cont.)
5441 603 GB
Service