Message
System characteristics Cause Measures
CB Primary temperature
Heat pump stops Min. primary flow tem-
perature (brine inlet) not
achieved
Primary circuit flow tem-
perature too low, no
measures required
CC Coding card
The coding card cannot
be read
Check coding card and
replace if required.
Check controller and
sensor PCB and
replace, if required.
CD KM BUS Vitocom
Communication error -
KM BUS Vitocom 100
Check Vitocom 100 con-
nections and connecting
cables.
Check connections at the
controller and sensor PCB
aVG
check KM BUS. A
fluctuating DC voltage
between approx. 20 V and
30 V can be measured at
the terminals.
CE KM BUS ext. extension
Communication error -
KM BUS external exten-
sion H1
Check external exten-
sion H1 connections and
connecting cables.
Check connections at the
controller and sensor PCB
aVG
check KM BUS. A
fluctuating DC voltage
between approx. 20 V and
30 V can be measured at
the terminals.
CF Communication module
Communication error -
LON module in control
unit
Check LON communica-
tion module and replace if
required.