Operating instructions
90
Valu
e
Explanation
"1" Instantaneous heating water
heater (accessory) is connected
and enabled for DHW reheating.
"0" Instantaneous heating water
heater (accessory) is not enabled
for DHW reheating.
Delivered condition 1
Setting 1 / 0
6005 Minimum temperature for DHW cylinder
"Minimum temperature 6005"
Lower set temperature for DHW cylinder
(minimum temperature).
When the actual temperature falls below
the minimum temperature selected, the
DHW cylinder is heated up to that value
plus hysteresis (frost protection). This is
independent of the selected operating
programme.
The temperature for this is always cap-
tured by the top cylinder temperature
sensor.
Delivered condition
100 (≙ 10 °C)
Setting range
50 to 600 (≙ 5 to 60 °C)
6006 Maximum temperature for DHW cylinder
"Maximum temperature 6006"
Upper temperature limit for DHW cylin-
ders.
When this temperature has been
reached, the DHW cylinder is not rehea-
ted until the temperature has dropped by
at least 5 K.
Danger
Risk of scalding with DHW at
temperatures above 60 ºC.
To limit the temperature to 60 °C,
install a mixing device, e.g. an
automatic thermostatic mixing
valve (DHW cylinder accessory).
Delivered condition
600 (≙ 60 °C)
Setting range
200 to 800 (≙ 20 to 80 °C)
Parameter group DHW
6015 DHW reheating
(cont.)
5441 603 GB