Operating instructions

91
"DHW hysteresis 6007"
"Booster heater hysteresis 6008"
Cylinder temperature hysteresis for
starting and stopping DHW heating.
The set value determines the deviation
from the set DHW cylinder temperature
("Cylinder temperature DHW 6000") at
which DHW heating is started and stop-
ped. Parameter "DHW hysteresis
6007" relates to DHW heating with the
heat pump. Parameter "Booster heater
hysteresis 6008" specifies the hystere-
sis for heating with the instantaneous
heating water heater (accessory).
t
A
Set DHW temperature
B
Heat pump hysteresis ("DHW hys-
teresis 6007")
C
Booster heater hysteresis ("Boos-
ter heater hysteresis 6008")
D
Actual DHW temperature at the top
cylinder temperature sensor
E
Heat pump switching state
F
Booster heater switching state
G
OFF
H
ON
Note
The value selected for "DHW hyste-
resis 6007" should be higher than the
expected temperature drop due to
heat losses while the heating circuits
are in reduced mode (approx. 5 K).
A lower value for "Booster heater
hysteresis 6008" increases the pro-
portion of DHW heating with the boos-
ter heater.
Observe setting for "DHW with e
heating 6015".
DHW hysteresis 6007 Booster heater hystere-
sis 6008
Delivered condition
70 ( 7 K) 100 ( 10 K)
Setting range
10 to 100 ( 1 to 10 K) 20 to 700 ( 2 to 70 K)
Parameter group DHW
6007/6008 DHW / Booster heater hysteresis
5441 603 GB
Service