Technical data

5683 718 - 04
10
Vitodens 200-W B2HA 100 to 150 Technical Data
System Flow Rates
Boiler B2HA 112 maximum flow rate; 38 GPM (8600 L/h)
Boiler B2HA 100 maximum flow rate; 25 GPM (5700 L/h)
Typical System Flow Rates
Boiler B2HA 150 maximum. flow rate; 38 GPM (8600 L/h)
Model B2HA 112 1 boiler 2 boilers 3 boilers 4 boilers 5 boilers 6 boilers 7 boilers 8 boilers
Output (NG/LPG)
MBH 375 750 1125 1500 1875 2250 2625 3000
rt for NG/LPG
20º F rise GPM
(L/h)
37.5
(8500)
75
(17000)
112.5
(25600)
150
(34100)
187.5
(42600)
225
(51100)
262.5
(59600)
300
(68100)
25º F rise GPM
(L/h)
30
(6800)
60
(13600)
90
(20400)
120
(27300)
150
(34100)
180
(40900)
210
(44700)
240
(54500)
30º F rise GPM
(L/h)
25
(5700)
50
(11400)
75
(17000)
100
(22700)
125
(28400)
150
(34100)
175
(39700)
200
(45400)
35º F rise GPM
(L/h)
21.4
(4900)
42.9
(9700)
64.3
(14600)
85.7
(19500)
107.1
(24300)
128.6
(29200)
150
(34100)
171.4
(38900)
40º F rise GPM
(L/h)
18.8
(4300)
37.5
(8500)
56.3
(12800)
75
(17000)
93.8
(21300)
112.5
(25600)
131.3
(29800)
150
(34100)
Model B2HA 150 1 boiler 2 boilers 3 boilers 4 boilers 5 boilers 6 boilers 7 boilers 8 boilers
Output (NG/LPG)
MBH 495 990 1485 1980 2475 2970 3465 3960
rt for NG/LPG
20º F rise GPM
(L/h)
49.5
(11243)
99
(22487)
149
(33731)
198
(44974)
247.5
(56213)
297
(67461)
346.5
(78705)
396
(89949)
25º F rise GPM
(L/h)
39.6
(8994)
79
(17990)
119
(26985)
158
(35979)
198
(44971)
237.6
(53969)
277
(62964)
317
(71959)
30º F rise GPM
(L/h)
33
(7495)
66
(14991)
99
(22487)
132
(29983)
165
(37476)
198
(44974)
231
(52470)
264
(59966)
35º F rise GPM
(L/h)
28
(6424)
57
(12850)
85
(19275)
113
(25700)
141.4
(32122)
170
(38549)
198
(44974)
226
(51399)
40º F rise GPM
(L/h)
25
(5631)
50
(11244)
74
(16865)
99
(22487)
124
(28107)
148.5
(33731)
173
(39352)
198
(44974)
Model B2HA 100 1 boiler 2 boilers 3 boilers 4 boilers 5 boilers 6 boilers 7 boilers 8 boilers
Output (NG/LPG)
MBH 333 666 999 1332 1665 1998 2331 2664
rt for NG/LPG
20º F rise GPM
(L/h)
33.3
(7563)
66.6
(15128)
100
(22692)
133
(30255)
166.5
(37816)
200
(45383)
233
(52947)
266.4
(60510)
25º F rise GPM
(L/h)
26.6
(6051)
53.3
(12102)
80
(18153)
106.6
(24204)
133
(30253)
160
(36307)
187
(42377)
213
(48409)
30º F rise GPM
(L/h)
22.2
(5042)
44.4
(10085)
66.6
(15128)
89
(20170)
111
(25211)
133
(30255)
155.4
(35298)
178
(40341)
35º F rise GPM
(L/h)
19
(4322)
38.1
(8644)
57
(12967)
76
(17289)
95
(21609)
114
(25933)
133
(30255)
152
(34578)
40º F rise GPM
(L/h)
16.7
(3781.6)
33.3
(7564)
50
(11346)
66.6
(15128)
83
(18908)
100
(22692)
117
(26473)
133
(30255)