Technical data

27
5683 718 - 04
Control Accessories
Vitotronic Control Accessories
Mixing Valve Extension Module
Rated voltage: 120 VAC
Rated frequency: 60 Hz
Rated current: 4 (2) A
Power consumption: 4 W
Max. ambient temp.
- at operation: 32 to 104º F (0 to 40º C)
- when storing
or transporting: -4 to+149º F (-20 to+65º C)
- Relay output for
heating circuit pump: 4 (2) A, 120 VAC
- Actuator torque: 3 Nm
- Time of 90º: 2 minutes
Mixing Valve Actuator Kit
The mixing valve actuator is mounted directly on the
Viessmann ¾ to 2½” mixing valve.
The mixing valve actuator is a motor-driven control unit.
The rotational direction is reversible.
The mixing valve actuator comes with a plug-in connector
for a heating circuit pump, supply temperature sensor
(strap-on sensor with 7 ft. (2.1 m) connecting cable),
power supply connecting cable 9 ft. (2.7 m) and a
connecting cable 9 ft. (2.7 m) for the KM-BUS Expansion
Module.
Rated voltage: 120 VAC
Rated frequency: 60 Hz
Rated current: 4 A
Power consumption: 5W max. ambient temperature
- at operation: 32º F to 104º F (0º C to 40º C)
application in living areas and installation sites
(normal ambient conditions)
-storage & shipping: -4º F to 149º F (-2C to 6C)
Max. relay outputs at 120 VAC for:
- Heating circuit pump: 1.0 A
- Mixing valve: 0.2 A
LON Communication Module
Electronic PCB for data exchange with the Vitotronic
200-H, Vitocom 200 and for connecting to a higher level
building management system.
LON Connecting Cable
(for data exchange between control units)
Cable length 23 ft. (7 m), fully wired
LON Terminal End Resistor
To terminate the LON BUS at the first and the last control
unit.
Vitodens 200-W B2HA 100 to 150 Technical Data
Immersion Temperature Sensor
To capture the low loss temperature
Specification
Lead length fully wired: 12 ft. (3.75 m),
Permissable ambient temp.
- during operation: 32 to 194° F (0 to 90° C)
- during storage and
transport: - 4 to+158° F (-20 to+70° C)