Technical data

5
5683 718 - 04
Vitodens 200-W B2HA 100 to 150 Technical Data
Technical Data
5
Technical Data (continued)
*A For high altitude installations 5,000 - 10,000 ft. (1500 m - 3000 m), the input for model B2HA 100 and 150 will
have an altitude de-ration of 14% for 5,000 ft. (1500 m) and 29% for 10,000 ft. (3000 m) average of 2.8% /
1,000 ft. (305 m). The input for model B2HA 112 at 10,000 ft. (3000 m) will have an input de-rate of 13%.
*4 Measured flue gas temperature with a combustion air temperature of 68° F (20° C).
*5 Based on maximum input rate.
*6 Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 200-W, B2HA for details.
*7 For side wall vent installations (coaxial system):
Do not exceed max. equivalent length specified in the Installation Instructions of the Vitodens 200-W, B2HA
Venting System.
Do not attempt to common-vent Vitodens 200-W with any other appliance.
Side wall co-axial vent installation must include Viessmann protective screen!
For details refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System.
*8 Add approximately 2b inches (65 mm) for coaxial vent pipe transition adaptor.
For information regarding other Viessmann System Technology componentry, please reference the documentation
of each respective product.
Boiler Model No. B2HA 100*A 112 150*A
Dimensions
Overall depth
Overall width
Overall height
inches
mm
inches
mm
inches
mm
21
530
19
480
43b
*8 1105
27.1
698
23
5
/
8
600
44b
*8 1128
27.1
698
23
5
/
8
600
44b
*8 1128
Flue gas *4
Temperature (at boiler return
temperature of 86º F (30º C)
- at rated full load
- at rated partial load
Temperature (at boiler return
temperature of 140º F (60º C)
ºF C)
ºF C)
ºF C)
135 (57)
99 (37)
162 (72)
124 (51)
102 (39)
158 (70)
140 (60)
102 (39)
165 (74)
Max. condensate flow rate *5
for NG and LPG
T
S
/T
R
=104/86º F (40/30º C) USG/h
L/h
3.5
13.1
4.35
16.5
5.28
20.0
Condensate connection *6 hose
nozzle
Ø in.
¾-1 ¾-1 ¾-1
Boiler flue gas connection *7 Ø
in. (mm) 4
3
/
8
(110) 4
3
/
8
(110) 4
3
/
8
(110)
Combustion air supply
connection (coaxial)
outer
Ø in. (mm) 6 (150) 6 (150) 6 (150)
Sound Rating
- at maximum input
- at minimum input
dB
dB
69
38
57
40
61
40