Operating instructions

76
Coding in the delivered condition Possible change
A6:36 Extended economy func-
tion disabled (only for
weather-compensated
control units)
A6:5
to
A6:35
Extended economy control
enabled, i.e. the burner and
heating circuit pump will be
stopped and the mixer
closed at a variable value,
adjustable between 5 and
35 °C plus 1 °C. The base
value is the adjusted out-
side temperature. This
value is based on the
actual outside temperature
and a time constant that
takes the cooling down of
an average building into
consideration.
A7:0 Without mixer economy
function (only for a
weather-compensated
control unit and heating
circuit with mixer)
A7:1 With mixer economy func-
tion (extended heating cir-
cuit pump logic):
Heating circuit pump also
"OFF":
If a mixer has been
closed for longer than
20 min.
Heating pump "ON":
If the mixer changes to
control function
If there is a risk of frost
A8:1 Heating circuit with mixer
creates a demand for the
internal circulation pump
(only for weather-com-
pensated control units)
A8:0 Heating circuit with mixer
creates no demand for the
internal circulation pump
A9:7 With pump idle time:
Heating circuit pump
"OFF" if the set value is
altered through a change
in operating mode or
through a change in the
set room temperature
(only for weather-com-
pensated control units)
A9:0 Without pump idle time
A9:1
to
A9:15
With pump idle time;
adjustable from 1 to 15
Code 2
Heating circuit 1, heating circuit 2, heating…
(cont.)
5692 857 GB