Operating instructions

109
Dis-
played
fault
code
Const. Weath.-
comp.
System char-
acteristics
Cause Measures
CE X X Control mode Communica-
tion error, ext.
extension
Check electrical
connections
CF X Control mode Communica-
tion error,
LON commu-
nication mod-
ule
Replace the LON
communication
module
d6 X X Control mode Input DE1
reports a fault
at extension
EA1
Remove fault at the
appliance con-
cerned
d7 X X Control mode Input DE2
reports a fault
at extension
EA1
Remove fault at the
appliance con-
cerned
d8 X X Control mode Input DE3
reports a fault
at extension
EA1
Remove fault at the
appliance con-
cerned
dA X Control mode
without room
influence
Short circuit,
room temper-
ature sensor,
heating circuit
1 (without
mixer)
Check room tem-
perature sensor,
heating circuit 1
db X Control mode
without room
influence
Short circuit,
room temper-
ature sensor,
heating circuit
2 (with mixer)
Check room tem-
perature sensor,
heating circuit 2
dC X Control mode
without room
influence
Short circuit,
room temper-
ature sensor,
heating circuit
3 (with mixer)
Check room tem-
perature sensor,
heating circuit 3
Troubleshooting
Fault codes
(cont.)
5457 552 GB