Operating instructions

133
Functions
One of the following circulation pumps
can be connected to each of the termi-
nals A1 and A2:
Heating circuit pump for the heating
circuit without mixer
Circulation pump for cylinder heating
DHW circulation pump
Allocating functions for outputs A1
and A2
Select the function for these outputs via
the codes on the boiler control unit:
Output A1: Code 33
Output A2: Code 34
Function Code
Output A1 Output A2
DHW circulation pump sK
33:0 34:0 (delivered
cond.)
Heating circuit pump
33:1 (delivered
cond.)
34:1
Circulation pump for cylinder heating sA
33:2 34:2
Function description
External extensions (accessories)
(cont.)
5457 552 GB
Service