Operating instructions
145
Air factor λ – CO
2
/O
2
content
Air factor λ O
2
content (%) CO
2
content (%) for nat-
ural gas H
CO
2
content (%) for
LPG P
1.24 4.4 9.2 10.9
1.27 4.9 9.0 10.6
1.30 5.3 8.7 10.3
1.34 5.7 8.5 10.0
1.37 6.1 8.3 9.8
1.40 6.5 8.1 9.6
1.44 6.9 7.8 9.3
To achieve an optimum combustion con-
trol, the system regularly carries out an
automatic self-calibration; also after a
power failure (shutdown). For this, the
combustion is briefly regulated to max.
ionisation current (equals air factor λ=1).
The automatic calibration is carried out
shortly after the burner start and lasts
approx. 5 s. During calibration, higher
than normal CO emissions may occur
briefly.
Function description
Electronic combustion controller
(cont.)
5457 552 GB
Service