Operating instructions

47
Selecting the upper/lower output for
weather-compensated control units:
1. Press OK and simultaneously for
approx. 4 s.
2. "Actuator test"
3. Select the lower output:
Select "Base load" "ON" and con-
firm with OK.
4. Select the upper output:
Select "Full load" "ON" and confirm
with OK.
Selecting the upper/lower output for
constant temperature control units:
1. Press OK and å simultaneously
for approx. 4 s.
"
Ü
" flashes on the display.
2. Select Ú " " and confirm with OK.
The display shows "I" and "on"
flashes.
3. Select the lower output:
Press OK, "on" will be displayed per-
manently.
4. Select the upper output:
Press
ä
.
5. Select "2" with Ú and confirm with
OK.
6. Exit output selection with ä.
Matching the control unit to the heating system
Subject to the equipment level, the control unit must be matched to the system. Var-
ious system components are recognised automatically by the control unit and the
relevant codes are adjusted automatically.
For the selection of an appropriate scheme, see the following diagrams.
For coding steps, see page 61.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5457 552 GB
Service