Operating instructions

57
Boiler control unit Vitotronic 200-H Vitotronic 200-H Vitocom
LON LON LON
Subscriber no. 1
Code "77:1"
Subscriber no. 10
Code "77:10"
Subscriber no. 11
Set code "77:11"
Subscriber no.
99
Control unit is fault
manager
Code "79:1"
Control unit is not
fault manager
Code "79:0"
Control unit is not
fault manager
Code "79:0"
Device is fault
manager
Control unit transmits
the time
Code "7b:1"
The control unit
receives the time
Set code "81:3"
The control unit
receives the time
Set code "81:3"
Device
receives the
time
Control unit transmits
outside temperature
Set code "97:2"
The control unit
receives the outside
temperature
Set code "97:1"
The control unit
receives the outside
temperature
Set code "97:1"
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber fault
monitoring
Code "9C:20"
Carrying out a LON subscriber check
Communication with the system devices connected to the fault manager is tested
with a subscriber check.
Preconditions:
The control unit must be programmed
as fault manager (code "79:1")
The LON subscriber number must be
programmed in all control units (see
page 57)
The LON subscriber list in the fault
manager must be up to date (see
page 57)
Carrying out a subscriber check:
1. Press OK and å simultaneously
for approx. 4 s.
2. "Service functions"
3. "Subscriber check"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5457 552 GB
Service