Installation and service instructions for heating engineers VitosolicĂ100 Electronic temperature differential control unit for solar heating system See Applicability on the last page.
Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety regulations Installation, initial start-up, inspection, maintenance and repairs must only be carried out by a competent person (heating engineer/installation contractor). Observe all current safety regulations as defined by DIN, EN, DVGW and VDE or locally applicable standards. See also the safety instructions sheet in the Vitotec technical documentation folder.
Index Index Page System designĂ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Installation and connections Control unit installationĂ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System design System design Dual mode DHW heating with VitocellĆBĂ100 or VitocellĆBĂ300 DHW heating without solar energy The upper indirect coil of the DHW cylinder is heated by a boiler. The cylinder thermostat with cylinder temperature sensorĂ6 of the boiler control unit switches cylinder loading pumpĂ7 . Ă ĂSafety instructions With temperatures higher than 60 ºC, limit the DHW temperature to 60 ºC by installing a mixing device, e.g. a thermostatic mixing valve (DHW cylinder accessory).
System design System design (cont.) 2 4A (slow) 1 S1 1 S2 2 3 4 230 V 50 Hz S3 5 7 8 A N R2 N R1 N L 145 6 12 13 14 15 16 17 18 19 20 4 STB R2 R1 9 WW C B 4 D 28 E F 5 5 *1 STB VL RL 6 8 21 7 3 5862Ă490ĂGB G A Solar panel B SolarĆDivicon C Draw-off point D DHW circulation E DHW circulation output of boiler control unit or on-site time switch *1High limit safety cut-out, see pageĂ8.
System design System design (cont.
Installation and connections Control unit installation Installation location Near the DHW cylinder, observing the electrical connections or their cable/lead lengths. 3. 5. 2. 1. 4. Make all electrical connections before closing the control unit. Electrical connections 1. Make all electrical connections in accordance with the details on pageĂ5. 5862Ă490ĂGB 2. Apply strain relief to cables.
Installation and connections Solar circuit pump Installation The "SolarĆDivicon" pump station includes the circulation pump with connecting cable. Alternative pumps must be type-tested and fitted in accordance with manufacturer's instructions. Connection (without connection extension) 3Ćcore cable with cross-section of 0.75Ămm2. Rated current: max.
Installation and connections Sensors Collector temperature sensor Installation Connection Collector installation instructions To S1 (terminals 1 and 2). Extension: 2Ćcore cable with cross-section of 1.5Ămm2. Cylinder temperature sensor The cylinder temperature is recorded indirectly through measuring the return temperature of the heat transfer medium inside the indirect coil. This results in enabling a reloading of the DHW cylinder through solar energy, even if only a little DHW is drawn off.
Installation and connections Mains electrical connection Regulations Carry out the mains connection and all earthing measures (e.g. fault current circuit) in accordance with IECĂ364, the requirements of your local electricity supplier, VDE regulations or all local and national regulations. The power supply to the control unit should be protected by a fuse with a max. rating of 16ĂA. Make the mains power supply connection (230ĂV~) via a mains isolator (two-pole) to be provided on site.
Initial start-up Steps Page 1. Probes or sensors correctly inserted into the sensor well?Ă 9 ............................ 2. Accessories correctly installed to respective installation instructions? 3. Electrical connections carried out correctly?Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 4. High limit safety cut-out connected to control unit and adjusted to 95ĂºC?Ă . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Initial start-up Further details regarding individual steps (cont.) Adjusting system settings At the setting level (see below), the following parameters and functions can be adjusted: Temperatures Differential temperatures . . . . . . . . . . . DO/DF Maximum cylinder temperatureĂ . . . SX ¨ Observe the max. permissible DHW temperature. Collector limit temperatureĂ . . . . . . . . . . . . ĂCL Maximum collector temperatureĂ ĂCX Minimum collector temperatureĂ . ĂCN Functions Max.
Initial start-up Further details regarding individual steps (cont.) Relay test 1. Select MM (manual mode) with "+" or "ć"; confirm with "OK"; SE flashes. RelayĂ1: RelayĂ2: OutputĂR1 OutputĂR2 2. Select the required setting with "+" or "ć": 0Ă:ĂRelayĂ1 and 2 OFF 1Ă:ĂRelayĂ1 ON, RelayĂ2 OFF 2Ă:ĂRelayĂ1 OFF, RelayĂ2 ON 3Ă:ĂRelayĂ1 and 2 ON always confirm with "OK". 5862Ă490ĂGB 3. Back to automatic mode with setting 4.
Service scans Temperatures Subject to system version, using "+" or "ć", the following temperatures can be scanned: Collector temperatureĂ . . . . . . . . . . . . . . . . . . . . . . . ĂTC Cylinder temperatureĂ . . . . . . . . . . . . . . . . . . . . . . . . . ĂTS Sensor or thermostat temperature (subject to selected function)Ă . . . . . . . . . . . . . . . . . . . . ĂT3 or TT Maximum cylinder temperatureĂ . . ĂSX Maximum collector temperatureĂ ĂCX Collector limit temperatureĂ . . . . . . . . . . . .
Troubleshooting Fault messages Sensor faults at S1 to S3 ( TC, TS, T3 or TT) are displayed by the ON/OFF display (flashes red) and through the following display.
Troubleshooting Checking sensors 860 1. Disconnect the relevant sensor and measure the resistance. 820 780 740 Resistance in 700 660 620 580 540 20 60 100 Temperature in ºC 140 180 Temperature in ºC Resistance in W 20 40 50 60 546 578 597 616 2. Compare measurement with the actual temperature displayed (for scanning, see pageĂ14). Check the installation and replace sensor if necessary, in the event of severe deviation.
Troubleshooting Changing the fuse A 4A (slow) 230 V 50 Hz S1 1 S2 2 3 S3 4 5 145 6 7 8 N R2 N R1 N L 12 13 14 15 16 17 18 19 20 A Fuse 5862Ă490ĂGB Open wiring chamber of control unit. Replacement fuse inside the pack.
System details/functions Summary Setting (as delivered condition) Setting range Explanation 0 to 8 0: No function Do not adjust if a sensor is connected to S3.
System details/functions Summary (cont.) Setting (as delivered condition) Setting range Explanation SXĂćĂMaximum cylinder temperature 2 to 90ĂºC Prevents the cylinder from further loading if the selected value has been exceeded. The maximum cylinder temperature control is factory activated by FNĂ=Ă1 (see pageĂ20). CLĂćĂCollector limit temperature 110 to 200ĂºC The solar circuit pump is switched OFF when this temperature has been exceeded to protect the solar components.
System details/functions Summary (cont.
System details/functions Special functions Maximum cylinder limit Select SFĂ=Ă1 at the setting level. The consumer connected to RĂ2 is started if the selected maximum cylinder temperature "SX" has been exceeded. Suppression of reloading by boiler Select SFĂ=Ă2 at the setting level. Systems with Vitotronic and Calotronic control units with KM BUS Connection of the KM BUS to terminals 7 and 8 in the solar control unit.
System details/functions Special functions (cont.
System details/functions Special functions (cont.) A R1 K1 R2 X3 1 2 3 4 5 PTC NTC Control unit 1 2 3 or or F L 5 WH M BN GN YE X5 or 21 22 23 24 5 G N X7 1 2 3 4 X7 or O 5862Ă490ĂGB X5 or A Connection extension F Cylinder temperature sensorĂ(NTC) G Cylinder temperature sensorĂ(PTC) L Vitotronic M Dekamatik*1 Viessmann Trimatik*1 Duomatik*1 *1Connecting PTC NTC P Unomatik*1 N Eurolamatik O Vitodens and Vitopend control unit P Pendola control unit cable, part no.
System details/functions Special functions (cont.) Additional function for DHW heating Only possible in conjunction with control unit with KM BUS (Vitotronic and Calotronic) and connection extension VitosolicĂ100. Connection of the KM BUS to terminals 7 and 8 in the solar control unit. Select SFĂ=Ă3 at the setting level. In systems with a capacity above 400Ălitres, the entire water content must be heated to 60ĂºC once every day.
System details/functions Maximum cylinder temperature control Select FNĂ=Ă1 at the setting level. The solar circuit pump is switched OFF if the set maximum cylinder temperatureĂ"SX" has been exceeded, to prevent overheating the DHW cylinder. When this function is active, the display will show ( Ăflashing) Collector cooling function Select FNĂ=Ă3 at the setting level. The solar circuit pump is switched OFF when the set maximum cylinder temperatureĂ"SX" is reached.
System details/functions Reverse cooling function Only set in systems with flat collector panels. Select FNĂ=Ă2 at the setting level. The solar circuit pump remains switched ON when the set maximum cylinder temperatureĂ"SX" has been reached, to prevent overheating the collector. In this case, the cylinder temperature may continue to rise, but no higher than 90ĂºC (cylinder safety shutdown). Please observe the safety instructions on pageĂ4.
Parts list Parts list When ordering spare parts Quote the part no. and the item no. of the required part (as per this parts list). Obtain common parts from your local supplier.
Appendix 175 Specification 110 Rated voltage: Rated frequency: Rated current: Power consumption: Safety class: Protection: Function: 46 230ĂV~ 50ĂHz 4ĂA 2ĂW II IPĂ20 to ENĂ60529, ensure through design/ installation TypeĂ1 B to ENĂ60730Ć1 Ă Permissible ambient temperature H in operation: 0 to +40ĂºC Installation in living accommodation and boiler rooms (normal ambient conditions) H in storage and transport: ć20 to +65ĂºC Rated relay output breaking capacity: 28 4 (2)ĂA, 230ĂV~ Ă
Appendix Declaration of conformity We, Viessmann Werke GmbH & CoĂKG, DĆ35107 Allendorf, declare as sole responsible body, that the product Ă Ă VitosolicĂ100 conforms to the following standards: ENĂ55014Ć1 ENĂ60730Ć1 This product is identified in accordance with the following guidelines: 89/336/EEC 73/ă23/EEC as follows: _ Allendorf, 1ĂJulyĂ2003 Viessmann Werke GmbH & CoĂKG Ă Ă 5862Ă490ĂGB pp.
Keyword index Keyword index B C Circulation pump,ă8 CL (collector limit temperature),ă14 CN (minimum collector temperature),ă14 Collector cooling function,ă19,ă25 Collector limit temperature,ă14,ă19 Collector minimum temperature,ă19 Collector temperature sensor,ă9 Commissioning,ă11 Connection and wiring diagrams,ă5 Connection extension,ă5,ă8,ă23 CX (maximum collector temperature),ă14 Cylinder, maximum temperature,ă19 Cylinder, maximum temperature control,ă25 Cylinder temperature.
Keyword index Keyword index (cont.
Applicability Applicability Viessmann Werke GmbHĂ&ĂCo DĆ35107 Allendorf Tel: +49 6452 70Ć0 Fax: +49 6452 70Ć27Ă80 www.viessmann.de Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Tel: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com 32 5862Ă490ĂGBăăăSubject to technical modifications. Printed on environmentally friendly, chlorine-free bleached paper. For control unit VitotronicĂ100, part no.