Installation and service instructions VIESMANN for contractors Vitotronic 300-K Type MW1B Weather-compensated cascade control unit Vitotronic 100 Type GC1B and GC4B Boiler control unit For applicability, see the last page VITOTRONIC 300-K VITOTRONIC 100 5815 091 GB 7/2013 Please keep safe.
Safety instructions Safety instructions Please follow these safety instructions closely to prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury. ! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively intended for qualified contractors.
Safety instructions Safety instructions (cont.) If you smell flue gas Danger The simultaneous operation of the boiler and appliances that extract air to the outside can result in life threatening poisoning due to reverse flow of the flue gas. Fit an interlock circuit or take suitable steps to ensure a sufficient supply of combustion air. Danger Flue gas can lead to life threatening poisoning. ■ Shut down the heating system. ■ Ventilate the installation site. ■ Close all doors in the living space.
Safety instructions Safety instructions (cont.) Repair work ! Please note Repairing components that fulfil a safety function can compromise the safe operation of the system. Faulty components must be replaced with original Viessmann spare parts. Auxiliary components, spare and wearing parts Please note Spare and wearing parts that have not been tested together with the system can compromise its function.
Index Index Installation instructions Intended use....................................................................................................... 9 Installation, Vitotronic 100 Overview of electrical connections....................................................................... Inserting cables and applying strain relief............................................................ Inserting the boiler coding card............................................................................
Index Index Service instructions Commissioning, Vitotronic 100 and Vitotronic 300-K Commissioning steps........................................................................................... Testing the high limit safety cut-out...................................................................... Selecting the language......................................................................................... Setting the date and time.......................................................................
Index Index Code 1, Vitotronic 100 Calling up coding level 1...................................................................................... 119 Group 1................................................................................................................ 119 Group 2................................................................................................................ 120 Code 2, Vitotronic 100 Calling up coding level 2................................................................
Index Index (cont.) Temperature limiter for limiting the maximum temperature.................................. 195 EA1 extension...................................................................................................... 196 Parts lists Parts list Vitotronic 100, type GC1B..................................................................... 199 Parts list Vitotronic 100, type GC4B..................................................................... 201 Troubleshooting Vitotronic 300-K............
Intended use Intended use The appliance is only intended to be installed and operated in sealed unvented heating systems that comply with EN 12828, with due attention paid to the associated installation, service and operating instructions. It is only designed for the heating of water that is of potable water quality. Installation Intended usage presupposes that a fixed installation in conjunction with permissible, system-specific components has been carried out.
Installation, Vitotronic 100 Overview of electrical connections ■ Observe the requirements of safety category II when connecting external switching contacts or components to the safety LV of the control unit. That is 8.0 mm air and creep paths and 2.0 mm insulation thickness against 'live' components. ■ Ensure the safe electrical separation of all on-site components (incl. PC/laptops) conforms to EN 60 335 or IEC 65.
Installation, Vitotronic 100 Overview of electrical connections (cont.
Installation, Vitotronic 100 Overview of electrical connections (cont.) Central fault message gÖ gSA1 Motorised butterfly valve or Motor for 3-way mixing valve for return temperature control lÖ aBÖ aBA aBH Burner stage 2/mod. External connections, e.g.
Installation, Vitotronic 100 Overview of electrical connections (cont.) gSA1 Motorised butterfly valve aBÖ External connections, e.g. supplementary safety equipment aBA aBH Safety chain, potential-free Power supply, from mains filter unit Inserting cables and applying strain relief 5815 091 GB Installation ■ Control unit fitted to the boiler: Route cables from below through the front panel of the boiler into the wiring chamber of the control unit.
Installation, Vitotronic 100 Inserting cables and applying strain relief (cont.) A D C D B A Cables with moulded strain relief B On-site cables; strip up to 100 mm of insulation. C Plug-in connection diagram D Female mouldings for plug-in connection diagram Inserting the boiler coding card 5815 091 GB Only use the boiler coding card supplied with the boiler (see page 185).
Installation, Vitotronic 100 Inserting the boiler coding card (cont.) Installation X7 Changing over the high limit safety cut-out Only Vitotronic 100, type GC1B The high limit safety cut-out is supplied with a factory setting of 110 °C.
Installation, Vitotronic 100 Changing over the high limit safety cut-out (cont.) 2. 1. 95 110 1 2 0 3. °C Changing the temperature controller setting Only Vitotronic 100, type GC1B The temperature controller is supplied with a factory setting of 95 °C. Please note Excessive DHW temperatures can damage the DHW cylinder. If the system operates with a DHW cylinder, ensure that the maximum permissible DHW temperature is not exceeded. If necessary, install suitable safety equipment for this purpose.
Installation, Vitotronic 100 Changing the temperature controller setting (cont.) A Installation 2. 1. 3. A 75 to 100 °C 1. Remove rotary selector " ". 5815 091 GB 2. Using a pair of pointed pliers, break tab A identified in the illustration out of the stop dial. 3. Fit rotary selector " " so that the marking lies at the centre of the selected range. Turn rotary selector " " fully clockwise.
Installation, Vitotronic 100 Inserting the LON communication module Making the LON connection, see page 44.
Installation, Vitotronic 100 Connecting sensors (cont.) aJA Therm-Control temperature sensor or Return temperature sensor T1 (accessory) aJB Return temperature sensor T2 (accessory) Vitotronic 100, type GC4B Installation Note No sensor connections are required. Connecting pumps Available connections sÖA1 Circulation pump, flue gas/water heat exchanger or Switching output Shunt pump or boiler circuit pump sL Pumps 230 V~ M A 1~ Rated current 4(2) A~ Recommended connecting cable H05VV-F3G 0.
Installation, Vitotronic 100 Connecting pumps (cont.) Pumps with power consumption greater than 2 A N L D L N L C N External ON/OFF B A Pump B To the control unit C Contactor L N PE A D Separate power connection (observe manufacturer's details) Pumps 400 V~ N L L1 L2 L3 N PE For switching the contactor Rated current 4(2) A~ Recommended connecting cable H05VV-F3G 0.75 mm2 or H05RN-F3G 0.
Installation, Vitotronic 100 Connecting actuators Available connections M 1~ 52 Vitotronic 100, type GC4B Motorised butterfly valve Rated voltage Rated current Recommended connecting cable Runtime 230 V~ Max. 0.2 (0.1) A~ H05VV-F4G0.75 mm2 or H05RN-F4G 0.75 mm2 5 to 199 s, adjustable at coding address "40" in group 1 "General". Open Close Connecting a central fault message facility L N 5815 091 GB 50 Rated voltage 230 V~ Rated current Max. 4 (2) A~ Recommended connecting cable H05VV-F3G 0.
Installation, Vitotronic 100 Connecting the external safety equipment Connection via plug aBÖ. The plug-in adaptor for external safety equipment (accessory, see chapter "Components") can be used for connecting several pieces of safety equipment. ! Please note 'Live' contacts lead to short circuits or phase failure. The external connections must be potential-free. Note Plug aBÖ must remain plugged in, even if no connection is made.
Installation, Vitotronic 100 Provisional burner operation STB EIN EIN N STB TR TR Insert jumper "TR" – " burner control unit ON/TR" across "TR" – "ON". The boiler heats up with burner stage 1 or with the lower heating output/base load.
Installation, Vitotronic 100 External burner blocking (cont.) Remove jumper "TR" – "ON/TR". A STB EIN EIN Note Connect only safety shutdown equipment, e.g. temperature limiter, to these terminals. Opening this contact leads to a controlled burner shutdown. N STB TR TR B A Floating contact B Jumper "TR" – "ON/TR" ! Please note The heating system has no frost protection while it is blocked. The boiler is not held at the lower boiler water temperature.
Installation, Vitotronic 100 External changeover of multi stage/modulating… (cont.) Code A Set code "02:2" in group 2. 1 2 3 Note When scanning the burner version, the address for modulation appears even after an external changeover (no rewriting). 146 Installation A External changeover (floating contact) Contact open: Modulating operation Contact closed: Two-stage operation Blocking the boiler externally/starting in the boiler sequence Connection at plug aVD.
Installation, Vitotronic 100 Blocking the boiler externally/starting in the… (cont.) Contact A Closed Open ■ The boiler is blocked and has The boiler is made part of the curbeen removed from the boiler rent boiler sequence. sequence. ■ Type GC1B: The motorised butterfly valve or the 3-way mixing valve for constant return temperature control are closed. Shunt pump or boiler circuit pump are switched off. Type GC4B: The motorised butterfly valve closes and the boiler circuit pump stops.
Installation, Vitotronic 100 Terminal codes L1 Phase via high limit safety cutout to the burner PE Earth conductor to burner N Neutral conductor to burner T1, T2 Control chain S3 Burner fault terminal B4 Hours run meter terminal Signal pass direction: Control unit → burner Signal pass direction: Burner → control unit 41 L1 TR N BZ Störung H1 N PE L1 N T1 T2 S3 B4 STB L 41 T1 T2 S3 B4 Equipment codes STB Control unit high limit safety cutout TR Control unit temperature controller H1 Burner faul
Installation, Vitotronic 100 Connecting the AC burner, type GC1B (cont.) 90 T6 T7T8 BN BK BU Terminal codes T6, T8 Control chain burner stage 2 ON or modulation controller Open T6, T7 Control chain burner stage 2 OFF or modulation controller Close Signal pass direction: Control unit → burner Signal pass direction: Burner → control unit Colour coding to DIN/IEC 60757 BK Black BN Brown BU Blue A To the control unit B To the burner Viessmann MatriX burner for Vitocrossal Max. power consumption 6 (3) A.
Installation, Vitotronic 100 A L N T1 T2 S3 B4 41 B4 S3 T2 T1 N Terminal codes L1 Phase via high limit safety cutout to the burner PE Earth conductor to burner N Neutral conductor to burner T1, T2 Control chain S3 Burner fault terminal B4 Hours run meter terminal Signal pass direction: Control unit → burner Signal pass direction: Burner → control unit L 41 B 5815 091 GB A To the control unit B To the burner 29 Installation Connecting the AC burner, type GC1B (cont.
Installation, Vitotronic 100 Connecting the AC burner, type GC1B (cont.
Installation, Vitotronic 100 Connecting the three-phase burner, type GC1B (cont.
Installation, Vitotronic 100 Connecting the three-phase burner, type GC1B (cont.
Installation, Vitotronic 300-K ■ Observe the requirements of safety category II when connecting external switching contacts or components to the safety LV of the control unit. That is 8.0 mm air and creep paths and 2.0 mm insulation thickness against 'live' components. ■ Ensure the safe electrical separation of all on-site components (incl. PC/laptops) conforms to EN 60 335 or IEC 65. 5815 091 GB Danger Incorrect wiring can lead to serious injury from electrical current and result in appliance damage.
Installation, Vitotronic 300-K Overview of electrical connections (cont.
Installation, Vitotronic 300-K Overview of electrical connections (cont.) sK sL fÖ gÖ gSA1 PCB 230 V~ sÖA1 Heating circuit pump or Primary pump, cylinder loading system Circulation pump for cylinder sA heating (accessory) aBH DHW circulation pump (on site) Distribution pump (on site) Power supply Central fault message Motor for 3-way mixing valve, cylinder loading system Power supply for accessories Installation Inserting cables and applying strain relief See page 13.
Installation, Vitotronic 300-K Connecting sensors (cont.) Fitting location for outside temperature sensor ■ North or north-westerly wall, 2 to 2.5 m above ground level; in multi storey buildings, in the upper half of the second floor. ■ Not above windows, doors or ventilation outlets. ■ Not immediately below balconies or gutters. ■ Never render over. Outside temperature sensor connection 2-core lead, up to 35 m long with a crosssection of 1.5 mm2 Wireless outside temperature sensor Wireless subscriber.
Installation, Vitotronic 300-K Connecting pumps (cont.) Pumps in the underfloor heating circuit B Temperature limiter C Secondary pump (downstream of the system separation) sÖ N 20 L Joint power consumption of both pumps: max.2 A A M 1~ B Installation M 1~ C sÖ Control unit A Primary pump Connecting actuators Available connections gSA1 Motor for 3-way mixing valve, cylinder loading system gSM2/M3 Mixer motor Connection, see page 21. 230 V~ Max. 0.2 (0.1) A~ H05VVF4G0.75 mm2 or H05RN-F4G 0.
Installation, Vitotronic 300-K Connecting a central fault message facility L Rated voltage 230 V~ Rated current Max. 4 (2) A~ Recommended connecting cable H05VV-F3G 0.75 mm2 or H05RN-F3G 0.75 mm2 N 50 Note All heating system faults are passed on. This includes boiler control unit faults, for example. External demand via switching contact Connection options: ■ Plug aVH ■ EA1 extension (accessory, see page 196) With the contact closed, the boiler burners are started subject to load.
Installation, Vitotronic 300-K External demand via switching contact (cont.) Plug aVH A EA1 extension DE [{A DE [{S B DE [{D 1 2 3 146 A Floating contact B Plug aVH of the control unit A Installation B A Floating contact B EA1 extension Codes Plug aVH No coding required. EA1 extension Set "5d" (DE1), "5E" (DE2) or "5F" (DE3) in the "General" group to 2. External demand via 0 – 10 V input Connection at input 0 – 10 V to EA1 extension (accessory, see page 196).
Installation, Vitotronic 300-K External demand via 0 – 10 V input (cont.) 0 – 1 V ≙ No default set flow temperature 1V ≙ Set value 10 °C 10 V ≙ Set value 100 °C Observe coding address "1E" in the "General" group. External blocking via switching contact Connection options: ■ Plug aVD ■ Extension EA1 (accessory, see page 196) ! Please note The heating system has no frost protection while it is blocked. The boilers are not held at the lower boiler water temperature.
Installation, Vitotronic 300-K External blocking via switching contact (cont.) Plug aVD A EA1 extension DE [{A DE [{S B DE [{D 1 2 3 143 A Floating contact B Plug aVD of the control unit Installation A B A Floating contact B EA1 extension Codes Plug aVD In coding address "99" in the "General" group determine, what the input should influence. EA1 extension Set "5d" (DE1), "5E" (DE2) or "5F" (DE3) in the "General" group to 3 or 4. External "Mixer close"/"Mixer open" Connection at plug aVD.
Installation, Vitotronic 300-K External "Mixer close"/"Mixer open" (cont.) A B 1 2 3 143 A External "Mixer open" (floating contact) B External "Mixer close" (floating contact) Codes External "Mixer open" In coding address "9A" in the "General" group, assign the function to the heating circuits. External "Mixer close" In coding address "99" in the "General" group, assign the function to the heating circuits.
Installation, Vitotronic 300-K External heating program changeover (cont.) Plug aVD A Extension EA1 The changeover can be achieved separately for heating circuits 1 to 3.
Installation, Vitotronic 300-K External heating program changeover (cont.) Codes Plug aVD Via coding address "91" in the "General" group, the function can be assigned to the heating circuits. Extension EA1 Set "5d" (DE1), "5E" (DE2) or "5F" (DE3) in group "General" to 1. Via coding address "d8" in the "Heating circuit..." group, the function can be assigned to the heating circuits.
Installation, Vitotronic 300-K Making the LON connection (cont.) Connection with Viessmann LON cable A A A C C B B Installation spacing ≤ 7 m C Terminator Installation A Control unit or Vitocom B LON cable, 7 m long Connection with Viessmann LON cable and coupling A A A C C B D B D B B D B D B Installation spacing 7 to 21 m A Control unit or Vitocom B LON cable, 7 m long Max.
Installation, Vitotronic 300-K Making the LON connection (cont.
Power supply of the Vitotronic 100 and Vitotronic 300-K Power supply Regulations Connect the power supply and implement all safety measures (e.g. RCD circuit) in accordance with IEC 60364, the connection requirements of your local power supply utility, and VDE or national regulations. Protect the power cable to the control unit with an appropriate fuse/MCB. Recommended power cable 3-core cable selected from the following options: ■ H05VV-F3G 1.5 mm2 ■ H05RN-F3G 1.
Power supply of the Vitotronic 100 and Vitotronic 300-K Power supply (cont.) 1. Check whether the power cable to the control unit is protected in line with regulations. L1 PE N BU GNYE BN 2. Terminate the power cable in the terminal box and at plug fÖ (on site). N L 40 3. Insert plug fÖ into the control unit.
Power supply of the Vitotronic 100 and Vitotronic 300-K Power supply (cont.) Power supply of the Vitotronic 100 via a mains filter unit 1. Check whether the power cable to the mains filter unit is protected in line with regulations. L1 PE N N L 40 3. Insert plug fÖ into the mains filter unit. Mains voltage 230 V~ Fuse/MCB Mains isolator, 2-pole (on-site) Junction box (on-site) 5815 091 GB A B C D Danger Incorrect wire assignment can result in serious injury and damage to the appliance.
Power supply of the Vitotronic 100 and Vitotronic 300-K Power supply (cont.) 4. Insert plug fÖ and plug aBH of the mains filter unit connecting cable into the appropriate control unit socket.
Opening and closing the Vitotronic 100 and Vitotronic 300-K control units Fitting the control unit front Note Step 1 applies only to the Vitotronic 300-K. 3. Installation 2. A 1. 7. 5. 4. 6. 8.
Opening and closing the Vitotronic 100 and Vitotronic 300-K control units Opening the control unit 2. 1. 5815 091 GB 3.
Commissioning, Vitotronic 100 and Vitotronic 300-K Commissioning steps Commissioning step Checking the high limit safety cut-out Selecting the language Setting the date and time Matching the coding addresses to the system version Selecting the boiler sequence Connecting the control unit to the LON Checking actuators and sensors Setting the heating curve Vitotronic 100 Page Type GC1B Type GC4B X — Vitotronic Page 300-K Type MW1B 53 — — — — — — — — X X 54 54 X X 54 X 56 — — — X 57 X X
Commissioning, Vitotronic 100 and Vitotronic 300-K Selecting the language Only Vitotronic 300-K, type MW1B At the commissioning stage, the display is in German (factory setting). Sprache Deutsch ç DE ê Bulgarski BG ê Cesky CZ ê Dansk DK ê Wählen mit ( Setting the date and time Only Vitotronic 300-K, type MW1B The time and date need to be reset during commissioning or after a prolonged time out of use.
Commissioning, Vitotronic 100 and Vitotronic 300-K Matching up the coding addresses (cont.) Code Group Function "01" 2 Multi boiler system "4d" 1 Plug sL function "98" 1 Viessmann system number "9C" 1 Monitoring LON subscribers Only for the Vitotronic 100, type GC1B: "0C" 2 Return temperature control "0d" 2 Therm-Control "4C" 1 Plug sÖ function "4E" 1 Plug gS function Matching the control unit to a two-stage burner Only Vitotronic 100, type GC1B Address 03:... Meaning Fuel 08:...
Commissioning, Vitotronic 100 and Vitotronic 300-K Matching up the coding addresses (cont.) Matching the control unit to a modulating burner Only Vitotronic 100, type GC1B Note The burner must be fully adjusted. To achieve a wide modulating range, set the minimum output as low as possible (take the chimney and flue system into account). Address 03:... Meaning Fuel 08:...
Commissioning, Vitotronic 100 and Vitotronic 300-K Matching up the coding addresses (cont.
Commissioning, Vitotronic 100 and Vitotronic 300-K Connecting the control unit to the LON ■ A LON communication module must be fitted into every Vitotronic 100 (see page 18). Installation and service instructions Vitotronic 200-H ■ Within one LON, each subscriber number must only allocated once. ■ Within a single LON, the system number (coding address "98" in the "General" group) must always be the same. ■ Only one Vitotronic may be programmed as fault manager.
Commissioning, Vitotronic 100 and Vitotronic 300-K Connecting the control unit to the LON (cont.) B With LON communication module. Code "76:1" in group 1 recognised automatically With LON communication module. Code "76:1" in group 1 recognised automatically C Control unit is not fault manager. Code "79:0" in group 1 With LON communication module. Code "76:1" in the "General" group recognised automatically — Number of connected boilers.
Commissioning, Vitotronic 100 and Vitotronic 300-K Connecting the control unit to the LON (cont.) A — B — C D E Control unit transmits outside temperature. Code "97:2" in the "General" group Control unit — receives the outside temperature. Set code "97:1" in the "General" group LON subscrib- LON subscriber LON subscrib- LON subscrib- — er remote mon- remote monitor- er remote er remote itoring. ing. monitoring. monitoring.
Commissioning, Vitotronic 100 and Vitotronic 300-K Connecting the control unit to the LON (cont.) Note ■ Vitotronic 100: During the subscriber check, the display for the relevant subscriber flashes for approx. 1 min. ■ Vitotronic 200-H: During the subscriber check, the display for the relevant subscriber flashes the subscriber no. for approx. 1 min and displays "Wink". Checking actuators and sensors Vitotronic 100 Carrying out a relay test Service menu: 1. Press OK and å simultaneously for approx. 4 s.
Commissioning, Vitotronic 100 and Vitotronic 300-K Checking actuators and sensors (cont.) Display 6 7 8 9 11 Explanation Actuator at output sL on Actuator at output gS open Actuator at output gS neutral Actuator at output gS close Central fault message at output gÖ on Note Connected pumps start during burner operation. Checking sensors Actual temperatures can be scanned in menu . Operating instructions Vitotronic 300-K Carrying out a relay test Service menu: 1. Press OK and approx. 4 s. 2.
Commissioning, Vitotronic 100 and Vitotronic 300-K Checking actuators and sensors (cont.) ON ON Explanation Central fault message at output gÖ Actuator at output sÖ M2 Open Close ON Actuator at output gS M2 Open Close ON Actuator at output gS M3 "AM1 output 1" "AM1 output 2" "Solar circuit pump" ON ON ON "Solar circ pmp min" ON "Solar circ pmp max" ON "SM1 output 22" ON Actuator at output sÖ M3 Contact " P - S" on plug aBJ of extension EA1 closed.
Commissioning, Vitotronic 100 and Vitotronic 300-K Adjusting the heating curve Only Vitotronic 300-K The heating curves represent the relationship between the outside temperature and the boiler water or flow temperature. To put it simply, the lower the outside temperature, the higher the boiler water or flow temperature. The boiler water or flow temperature in turn affects the room temperature. Settings in the delivered condition: ■ Slope = 1.4 ■ Level = 0 1.8 100 1.6 80 1.2 70 1.0 60 0.8 50 0.
Commissioning, Vitotronic 100 and Vitotronic 300-K Adjusting the heating curve (cont.) The heating curve is offset along the set room temperature axis. With the heating circuit pump logic function enabled, the curve modifies the starting and stopping characteristics of the heating circuit pump.
Commissioning, Vitotronic 100 and Vitotronic 300-K Adjusting the heating curve (cont.) 110 Boiler water or Flow temperature in °C 3.4 1.4 A B 0.2 +20 -20 Outside temperature in °C A Changing the slope B Changing the level (vertical parallel offset of the heating curve) Extended menu: 1. 2. "Heating" 3. Possibly / for the required heating circuit 4. "Heating curve" 5. "Slope" or "Level" 6. Set values according to system requirements. Example: Heating curve setting with slope 1.
Service scans, Vitotronic 100 Calling up the service menu Service menu: 1. Press OK and simultaneously for approx. 4 s. flashes on the display. 2. / for the required function (see the following table). Symbol Code 1 Code 2 Function Diagnosis Relay test Fault history Coding level 1 Coding level 2 Exiting the service menu 1. With select SERV 7. 2. OK to confirm; "OFF" flashes. 3. OK to confirm Note The system exits the service menu automatically after 30 min.
Service scans, Vitotronic 100 Brief scan (cont.
Service scans, Vitotronic 100 Service indicator After the limits set at coding address "1F", "21", "23" in group 2 have been reached, the red fault indicator begins to flash and the display shows the following messages: ■ The specified hours run and . ■ The specified interval with and . ■ The specified maximum flue gas temperature and ; only for the Vitotronic 100, type GC1B. a 150 °C Acknowledging the service display Press OK to acknowledge a service message.
Service scans, Vitotronic 300-K Calling up the service menu Service menu: 1. Press OK and simultaneously for approx. 4 s. 2. / for the required menu (see the following diagram).
Service scans, Vitotronic 300-K Scanning operating data (cont.) Service menu: 1. Press OK and simultaneously for approx. 4 s. 2. "Diagnosis" 3. / for the required group, for example "General". Note "- - -" appears on the display if a scanned sensor is faulty. For further information on operating data, see chapter "Brief scan". Resetting operating data Saved operating data (e.g. hours run) can be reset to 0. The value "Adjusted outside temp" is reset to the actual value. Service menu: 1.
Service scans, Vitotronic 300-K 2: 1 2 System schemes 01 to 10 0 0 3 4 Software version, control unit 0 3: 0 0 Number of KM BUS subscribers 4: 5: 0 0 0 0 0 0 6: 7: 0 0 Subnet address/system number SNVT Software config. version 0: Auto Com1: Tool munic. coproc.
Service scans, Vitotronic 300-K Brief scan (cont.) 1 11: 0 2 0 3 Software 0 version, extension for heating circuits 2 and 3 with mixer 4 5 Software 0 version, extension for heating circuits 2 and 3 with mixer 6 Note The displays in fields 3 and 5 are the same. Service indicator No service interval can be set at the Vitotronic 300-K. No service message will be displayed. If a service message is active on any Vitotronic 100, the display of the Vitotronic 300-K will show "Service" and will flash.
Troubleshooting Vitotronic 100 Fault display In the event of a fault, the red fault indicator flashes at the control unit. The 2digit fault code and flash on the display. Note Any connected central fault message facility starts. Example: Fault code "d1" burner fault ã 1 d1 Other current faults can be displayed with / . For an explanation of the fault code, see chapter "Fault codes". Acknowledging fault messages Press OK; the default display appears.
Troubleshooting Vitotronic 100 Fault display (cont.) Deleting fault history While the list is displayed, press OK until flashes. OK to confirm. Fault codes 30 38 Type GC1B: The burner is started and stopped via the temperature controller. Type GC1B: The burner is started and stopped via the temperature controller. Type GC1B: Boiler with maximum temperature, no output reduction, mixing valve return temperature control open Type GC4B: Boiler at maximum temperature Measures Service the appliance.
Troubleshooting Vitotronic 100 Fault codes (cont.) System characteristics Type GC1B: Boiler with maximum temperature, no output reduction, mixing valve return temperature control open Type GC4B Boiler at maximum temperature 70 Type GC1B: Shunt pump constantly ON. Type GC4B: Control mode 78 Type GC1B: Shunt pump constantly ON. Type GC4B: Control mode A0 Boiler cools down. A1 Boiler cools down.
Troubleshooting Vitotronic 100 Fault codes (cont.) A3 AA AC Ad b0 Measures Check safety equipment, and reset if required. Check safety equipment, and reset if required. Insert plug aJA. For the Vitocrossal code "0d:0" in group 2 must be set. Insert plug aJA and check codes. With motorised butterfly valve: set code "4E:0" in group 1. Without motorised butterfly valve: set code "0C:1" in group 2. Check the flue gas temperature sensor (see page 186).
Troubleshooting Vitotronic 100 Fault codes (cont.) Displayed fault code b5 System characteris- Cause tics Control mode Internal error b6 Constant mode Invalid hardware recognised Measures Check PCB and plug-in connection; replace PCB if required. Check coding address "92" in group 1: Type GC1B: "92:161" Type GC4B: "92:166" Note Code "8A:176" in the group 1 must be set for coding address "92" to be displayed. b7 b8 bF Boiler coding card fault Plug in or replace boiler coding card.
Troubleshooting Vitotronic 100 Fault codes (cont.) C9 CA Cb 5815 091 GB CE System characteris- Cause tics Boiler cools down. Fault, low water indicator at "X7" of plug-in adaptor 1 for external safety equipment Boiler cools down. Fault, maximum pressure limiter at "X3" of plug-in adaptor 1 for external safety equipment Boiler cools down. Fault, minimum or maximum pressure limiter 2 at "X2" of plug-in adaptor 1 for external safety equipment Boiler cools down.
Troubleshooting Vitotronic 100 Fault codes (cont.) Displayed fault code d2 System characteris- Cause tics Control mode Communication error, plug-in adaptor 2 for external safety equipment d4 Boiler cools down. Measures Check the plug-in adaptor (see page 187). Without plug-in adaptor: Set code "31:0" in group 1. The high limit safe- Check the high limit safety ty cut-or MCB/ cut-out or the burner, fuse F2 has tripburner loop and MCB/ ped/blown. fuse F2.
Troubleshooting Vitotronic 100 Fault codes (cont.) E2 E2 E3 E4 E5 EE EF Check setting of gas pressure switch 2; check connecting cable; replace gas train. Check setting of gas pressure switch 2; check connecting cable; replace gas train. Replace gas train. Check strapping plug fJ. Check the power supply. Replace burner control unit. Reset burner control unit; replace burner control unit. Reset burner control unit; replace burner control unit. Check plug and KM BUS to burner control unit.
Troubleshooting Vitotronic 100 Fault codes (cont.) F1 F2 F3 F4 Cause Measures Excessive flue gas temperature; excessive gas throughput. Wait until temperature undershoots the permissible flue gas temperature. Reset burner control unit. Check water level; check heat exchanger surfaces for contamination; check CO2 setting; set gas throughput according to rated heating output of boiler (for connection values, see boiler service instructions).
Troubleshooting Vitotronic 100 Fault codes (cont.) F4 F4 F4 F4 F5 5815 091 GB F5 Cause Measures Insulation body of ignition or ionisation electrode cracked. Replace ignition or ionisation electrode. Servomotor faulty, servomotor connecting cable faulty, output relay faulty (burner control unit). Flame does not build Incorrect gas type during the safety selected. time, no signal reported by the ionisation flame monitor. Flame does not build Gas train does not during the safety open.
Troubleshooting Vitotronic 100 Fault codes (cont.) F6 F7 F7 F8 System characteristics Gas pressure switch reports no gas pressure. Cause Measures Gas shut-off valve closed; gas pressure switch faulty; multiple problems with gas supply. Fan pressure is produced during the air pressure switch idle state check. Air pressure switch contact is not in the idle state. Flame extinguishes during operation. Wind influence on fan.
Troubleshooting Vitotronic 100 Fault codes (cont.) F9 FA Measures Check cable a-ÖA and external power supply. Replace cable and fan if necessary. Check flue outlet, wind influence on fan and fan itself. Possibly replace components. Read off fault at the burner control unit display and programming unit (boiler service instructions). 5815 091 GB Service Fd System characteris- Cause tics ■ Fan faulty. No fan feedback. ■ Fan may be blocked by dirt. ■ External fan power supply not connected or faulty.
Troubleshooting Vitotronic 300-K Fault display In the event of a fault, the red fault indicator flashes at the control unit. "Fault" is displayed and flashes. The fault code is displayed with OK. For an explanation of fault codes, see chapter "Fault codes". For some faults, the type of fault is also displayed in plain text. Note Any connected central fault message facility starts. Acknowledging fault messages Follow the instructions on the display. Note The fault message is transferred to the menu.
Troubleshooting Vitotronic 300-K Fault display (cont.) Press OK and approx. 4 s. simultaneously for Fault history Display? Delete? Select with ( Fault codes 18 19 Cause Measures Short circuit, outside temperature sensor Lead break, outside temperature sensor Communication error, wireless outside temperature sensor Check outside temperature sensor (see page 186).
Troubleshooting Vitotronic 300-K Fault codes (cont.) 40 System characteristics Standalone control unit without flow temperature sensor (flow temperature may not be high enough). Mixer is being closed. 44 Mixer is being closed. 48 Mixer is being closed. 4C Mixer is being closed. 50 Cylinder loading pump on: Set DHW temperature = set flow temperature Priority control is cancelled. Or With cylinder loading system: Cylinder heating is started and stopped via cylinder temperature sensor 2.
Troubleshooting Vitotronic 300-K Fault codes (cont.) 58 59 60 Cause Measures Short circuit, cylinder temperature sensor 2 Check cylinder temperature sensor (see page 185). Short circuit, cylinder temperature sensor 1 Check cylinder temperature sensor (see page 185). Short circuit, cylinder temperature sensor 2 Check cylinder temperature sensor (see page 185). Short circuit, temperature sensor aJA Check temperature sensor (see page 185).
Troubleshooting Vitotronic 300-K Fault codes (cont.) 90 System characteristics Shunt pump constantly ON. With cylinder loading system: close 3-way mixing valve; no DHW heating Shunt pump constantly ON. With cylinder loading system: close 3-way mixing valve; no DHW heating Control mode 91 Control mode 92 No solar DHW heating 93 Control mode 78 90 Cause Measures Short circuit, temperature sensor aJB Check temperature sensor (see page 185).
Troubleshooting Vitotronic 300-K Fault codes (cont.) 98 System characteris- Cause tics No solar DHW heat- Short circuit, cylining der temperature sensor, connection of temperature sensor % at solar control module, type SM1 or sensor at S2 of the Vitosolic Control mode Lead break, temperature sensor /, connection at solar control module, type SM1 Control mode 9A No solar DHW heating 9b Control mode Check sensor at the solar control unit (see separate installation and service instructions).
Troubleshooting Vitotronic 300-K Fault codes (cont.) 9E 9F A7 Ab b1 92 System characteris- Cause tics No solar DHW heat- Lead break, cylining der temperature sensor, connection of temperature sensor % at solar control module or sensor at S2 of the Vitosolic Control mode No flow rate in solar circuit or flow rate too low, or temperature limiter has responded.
Troubleshooting Vitotronic 300-K Fault codes (cont.) Displayed fault code b5 System characteris- Cause tics Control mode Internal error b6 Constant mode Invalid hardware recognised Measures Check PCB is plugged in correctly. Check coding address "92" in the "General" group; "92:187" must be set.
Troubleshooting Vitotronic 300-K Fault codes (cont.) Displayed fault code bd bE bF Measures Check connections, cable (see separate installation and service instructions) and coding address "A0" in the "Heating circuit..." group. With wireless remote control: Place the remote control near the wireless base station and check connection (see separate installation and service instructions).
Troubleshooting Vitotronic 300-K Fault codes (cont.) Displayed fault code CF System characteristics Control mode No communication via LON Cause Measures Communication error, control unit LON communication module d3 Control mode Communication error, EA1 extension d5 Boiler ramps to the electronic maximum boiler water temperature limit. Control mode Check LON communication module and replace if required. If no LON communication module is installed, set code "76:0" in the "General" group.
Troubleshooting Vitotronic 300-K Fault codes (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Boiler control unit Vitotronic 100, type GC1B Brief description ■ The boiler water temperature is regulated by starting and stopping the burner or through modulation. ■ The set boiler water temperature is specified by the Vitotronic 300-K cascade control unit. ■ The boiler coding card specifies a minimum boiler water temperature that must be maintained to protect the boiler.
Function description, Vitotronic 100 and Vitotronic 300-K Boiler control unit Vitotronic 100, type GC1B (cont.) Switching hysteresis, burner Permanent switching hysteresis Code "04:0" Burner ON Time OFF +2 set -2 low heat demand average heat demand high heat demand Heat demand-dependent switching hysteresis The heat demand-dependent switching hysteresis takes the boiler load into account. The switching hysteresis, i.e the burner runtime varies subject to actual heat demand.
Function description, Vitotronic 100 and Vitotronic 300-K Boiler control unit Vitotronic 100, type GC1B (cont.) Burner ON Time OFF +17 +3 set -3 low heat demand average heat demand high heat demand Control sequence Boiler goes cold Boiler heats up (set value −2 K) The burner start signal is set as the set boiler water temperature minus 2 K. The burner starts its own monitoring program. (set value +2 K) The burner shuts down.
Function description, Vitotronic 100 and Vitotronic 300-K Boiler control unit Vitotronic 100, type GC4B Brief description ■ The boiler water temperature is regulated by modulating the burner.
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.) Standalone control Boilers connected in series ■ Without and with flow temperature sensor (see the following table). ■ The control strategy is set automatically to conventional boiler strategy 2, code "3C:2" in the "Cascade" group (see page 104). ■ The cascade control defaults the set boiler water temperature for all currentThe following control strategies are availly active boilers.
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.) ■ The control strategy is set automatically to conventional boiler strategy 2, code "3C:2" in the "Cascade" group (see page 104). ■ The cascade control unit regulates to the defaulted set flow temperature by defaulting the output for each individual boiler. The lead boiler can be operated in modulating mode. All other boilers are operated in two stages via a defaulted output (incl. modulating burners).
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.) Conventional boiler strategies Benefit Starting criterion Conventional boiler strategy 2 Long burner runtimes. Code "3C:2" in the "Cascade" group (delivered condition). An additional boiler will only be started if the maximum output of all currently active burners is insufficient to achieve the set flow temperature.
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Cascade control of the Vitotronic 300-K (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) Functions Time program The control unit switches over according to the time program. In the "Heating and DHW" operating program, the control unit switches between "Central heating with standard room temperature" and "Central heating with reduced room temperature". Every operating mode has its own set level. 4 time phases per day can be selected.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) DHW temperature Priority control ■ With priority control: (code "A2:2" in the "Heating circuit..." group): The set flow temperature will be adjusted to 0 °C during cylinder heating. The mixer closes and the heating circuit pump is switched off. ■ Without priority control: The heating circuit control unit continues to operate with the same set value.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) ■ The report to be provided by the heating contractor must contain the following details on heat-up: – Heat-up data with respective flow temperatures – Max. flow temperature achieved – Operating conditions and outside temperature during handover of the heating system ■ The various temperature profiles are adjustable via coding address "F1" in the "Heating circuit..." group.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) Flow temperature °C Temperature profile 7: Code "F1:15" 50 40 30 20 10 1 5 10 15 20 25 30 Days System dynamics Frost protection You can influence the control characteristics of the mixers at coding address "C4" in the "Heating circuit..." group. The flow temperature is maintained in accordance with the heating curve for the reduced set room temperature, but at min. 10 °C.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) Flow temperature control 110 Flow temperature in °C +8 K B 80 A D C 8K E +20 -20 Outside temperature in °C A Maximum flow temperature limit (coding address "37" in the "Cascade" group) B Slope = 1.8 for heating circuit without mixer C Slope = 1.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) Example using the settings in the delivered condition Boiler water or Flow temperature in °C 90 80 A 70 60 50 B 40 35 30 3 Se 0 2 t ro 5 om tem 20 10 5 per 15 atu 1 re in ° 0 5 C 0 -5 -10 -15 -20 Outside temp.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.
Function description, Vitotronic 100 and Vitotronic 300-K Heating circuit control of the Vitotronic 300-K (cont.) Flow temperature rises (Set value +1 K) The mixer motor receives the signal "Mixer closed". The signal duration lengthens with an increasing control differential. The duration of pauses reduces with an increasing control differential. Cylinder temperature control of the Vitotronic 300-K Brief description ■ The cylinder temperature control is a constant temperature control function.
Function description, Vitotronic 100 and Vitotronic 300-K Cylinder temperature control of the Vitotronic… (cont.) In conjunction with coding address "7F" in the "General" group ■ Detached house Code "7F:1": – Automatic mode The heating times for heating circuit 1 are applied to systems with two or three heating circuits. – Individual time program The time phases for DHW heating and the DHW circulation pump have the same effect on all heating circuits.
Function description, Vitotronic 100 and Vitotronic 300-K Cylinder temperature control of the Vitotronic… (cont.) System with cylinder loading system System with solar control unit The above functions also apply in conjunction with cylinder loading systems. Set the following codes: "55:3" in the "DHW" group; "4C:1", "4E:2" in the "General" group. The DHW cylinder is only reheated by the boiler if the temperature falls below this value.
Function description, Vitotronic 100 and Vitotronic 300-K Cylinder temperature control with 2 cylinder temperature sensors (code "55:2") Code "55:3" in the "DHW" group, cylinder temperature control, cylinder loading system Cylinder temperature sensor 1 enables the circulation pump for cylinder heating and is evaluated for stop conditions during the pump run-on time. Cylinder temperature sensor 2: Cylinder heating will start early if a lot of hot water is drawn off.
Code 1, Vitotronic 100 Calling up coding level 1 Note Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed. The codes are divided into groups: 1 "General" 2 "Boiler" 6 "All codes std device". In this group, all coding addresses are displayed in ascending order. 7 "Standard setting" 3. / for the group of the required coding address 4. / for the required coding address 5. / for the required value according to the following tables 6.
Code 1, Vitotronic 100 Group 1 (cont.) Coding in the delivered condition Servomotor runtime 40:... Actuator runtime at plug gSA1 Delivered condition defaulted by boiler coding card. Subscriber no. 77:1 LON subscriber number Possible change 40:5 to 40:199 Runtime adjustable from 5 to 199 s. 77:1 to 77:99 LON subscriber number, adjustable from 1 to 99 Group 2 Coding Burner type 02:1 Type GC1B: Two-stage burner Gas/oil operation 03:0 Type GC1B: Gas operation Boiler/burner 05:...
Code 1, Vitotronic 100 Group 2 (cont.) Coding in the delivered condition Boiler 07:1 Consecutive boiler number in multi boiler systems Flue gas monitor 1F:0 Flue gas temperature is not monitored for service indicator Possible change 07:2 to 07:4 Consecutive boiler number in multi boiler systems 1F:1 to 1F:250 is displayed if the flue gas temperature limit is exceeded. Limit adjustable from 1 to 250 °C. Burner service in 100 hours 21:0 No service interval (hours 21:1 run) selected.
Code 2, Vitotronic 100 Calling up coding level 2 Note ■ All codes are accessible in coding level 2. ■ Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed. ■ For code groups, see page 119 Service menu: 1. Press OK and simultaneously for approx. 4 s. flashes on the display. 2. Press OK and simultaneously for approx. 4 s. 3. Select 2 with to reach coding level 2. Confirm with OK. I flashes on the display for the coding addresses of group 1. 4.
Code 2, Vitotronic 100 Group 1 (cont.) 4A:1 4b:0 No sensor aJB installed 4b:1 4C:2 Connection on plug sÖ: Therm-Control contact 4C:1 4C:3 4d:1 Connection on plug sL: Shunt pump 4d:2 4d:3 4E:0 Connection on plug gS: Motorised butterfly valve 4E:1 4F:5 6C:0 6d:0 5815 091 GB Possible change 33:3 Circulation pump for neutralising system or flue gas/ water heat exchanger 34:3 Circulation pump for neutralising system or flue gas/ water heat exchanger 40:5 Runtime adjustable from 5 to to 199 s.
Code 2, Vitotronic 100 Group 1 (cont.) 77:1 78:1 79:0 80:6 88:0 8A:175 8b:0 93:0 98:1 9b:0 9C:20 9d:0 124 Possible change 76:1 With LON communication module; recognised automatically. LON subscriber number 77:1 LON subscriber number, to adjustable from 1 to 99. 77:99 LON communication en- 78:0 LON communication disaabled. bled. Control unit is not fault 79:1 Control unit is fault managmanager. er.
Code 2, Vitotronic 100 Group 2 Coding 02:1 03:0 04:... 05:... 06:87 07:1 5815 091 GB 08:... Possible change 01:2 Multi boiler system with cascade control via LON 01:3 Never adjust Type GC1B: 02:0 Single stage burner Two-stage burner 02:2 Modulating burner Type GC1B: 03:1 Oil operation (irreversible) Gas operation 03:2 Set automatically if no boiler coding card or an incorrect boiler coding card is inserted.
Code 2, Vitotronic 100 Group 2 (cont.) Coding in the delivered condition Delivered condition defaulted by the boiler coding card. 09:... Type GC1B: Maximum burner output in kW Delivered condition defaulted by the boiler coding card. 0A:... Type GC1B: Burner base output in kW Delivered condition defaulted by the boiler coding card. 0C:5 Motorised butterfly valve modulating independent of the set boiler water temperature Possible change 09:0 to 09:199 Maximum output adjustable from 0 to 19,900 kW.
Code 2, Vitotronic 100 Group 2 (cont.) 16:... 1A:... 1b:60 14:0 to 14:15 Minimum runtime adjustable from 0 to 15 min. 15:5 to 15:199 Runtime adjustable from 5 to 199 s. For the Vitocrossal, see separate service instructions. Offset adjustable from 0 to 15 K. 16:0 to 16:15 1A:0 to 1A:60 Duration of start optimisation adjustable from 0 to 60 min. 1b:0 to 1b:199 Control delay adjustable from 1 to 199 s. 1C:1 to 1C:199 Delay adjustable from 1 to 199 s.
Code 2, Vitotronic 100 Group 2 (cont.) Coding in the delivered condition Possible change Compensation of signal That is operating situations delay for hours run meter. where the burner is shut Time from burner start down via the mechanical signal initiation at T2 in temperature controller, but a burner demand is still plug fA to opening of the present (hours run continsolenoid valve. At each ue to be counted). burner start, 120 s will be If required, change coding taken off the runtime. address "06".
Code 2, Vitotronic 100 Group 2 (cont.) 29:0 2A:0 2b:5 Type GC1B: Burner fuel consumption (stage 1 and 2), no count if "29:0" and "2A:0" are programmed. Type GC1B: Burner fuel consumption (stage 1 and 2), no count if "29:0" and "2A:0" are programmed. Maximum preheating time of the motorised butterfly valve 5 min Maximum run-on time of the motorised butterfly valve 5 min 2d:0 Type GC1B: Shunt pump control function only ON if the boiler is enabled.
Code 1, Vitotronic 300-K Calling up coding level 1 Note ■ The codes are displayed as plain text. ■ Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed. ■ Heating systems with one heating circuit without mixer and one or two heating circuits with mixer: The heating circuit without mixer is designated "Heating circuit 1" and the heating circuits with mixer as "Heating circuit 2" or "Heating circuit 3".
Code 1, Vitotronic 300-K "General" group (cont.) Value adDescription dress 00: ... 2 One heating circuit without mixer A1 (heating circuit 1), with DHW heating; recognised automatically. 3 One heating circuit with mixer M2 (heating circuit 2), without DHW heating. 4 One heating circuit with mixer M2 (heating circuit 2), with DHW heating. 5 One heating circuit without mixer A1 (heating circuit 1), one heating circuit with mixer M2 (heating circuit 2), without DHW heating; recognised automatically.
Code 1, Vitotronic 300-K "General" group (cont.
Code 1, Vitotronic 300-K "Cascade" group (cont.) Coding in the delivered condition Max. system flow temperature 37:80 Electronic maximum system flow temperature limit set to 80 °C. Possible change 37:20 to 37:127 Maximum limit adjustable from 20 to 127 °C Note Value must be lower than the lowest value of coding address "06" in group 2 of every Vitotronic 100.
Code 1, Vitotronic 300-K "DHW" group Coding Coding in the delivered condition DHW 67:40 For solar DHW heating: Set DHW temperature 40 °C. Reheating is suppressed above the selected set temperature (DHW heating by the boiler only if there is insufficient solar energy). Enable DHW circulation pump 73:0 DHW circulation pump: ON according to time program Possible change 67:0 67:10 to 67:95 No set value 3 Set DHW temperature adjustable from 10 to 95 °C (limited by boiler-specific parameters).
Code 1, Vitotronic 300-K "Solar" group (cont.) Possible change 0A:0 0A:1 to 0A:40 Stagnation time reduction disabled. Temperature differential adjustable from 1 to 40 K. 0F:1 to 0F:255 Flow rate adjustable from 0.1 to 25.5 l/min; 1 step ≙ 0.1 l/min. 20:1 Additional function for DHW heating. Differential temperature control 2. Differential temperature control 2 and ausiliary function. Differential temperature control 2 for central heating backup. Thermostat function.
Code 1, Vitotronic 300-K "Heating circuit ...
Code 1, Vitotronic 300-K "Heating circuit ..." group (cont.
Code 1, Vitotronic 300-K "Heating circuit ..." group (cont.
Code 1, Vitotronic 300-K 5815 091 GB Coding in the delivered condition Possible change Heating program changeover d5:0 With external operating d5:1 Changeover to "Constant program changeover (oboperation with standard serve setting of coding room temperature" addresses "5d", "5E", "5F" and "91" in the "General" group). Changeover "Constant central heating with reduced room temperature" or "Standby mode" (subject to set reduced room temperature) Ext.
Code 1, Vitotronic 300-K "Heating circuit ..." group (cont.) Coding in the delivered condition Party mode time limit F2:8 Time limit for party mode or external operating program changeover via pushbutton: 8 h*2 Possible change F2:0 F2:1 to F2:12 No time limit*2 Time limit adjustable from 1 to 12 h*2. F8:+10 to F8:–60 F8:–61 Temperature limit adjustable from +10 to –60 °C.
Code 1, Vitotronic 300-K "Heating circuit ..." group (cont.) 5815 091 GB Service Coding in the delivered condition Possible change Duration set flow temperature increase Fb:30 Duration for raising the Fb:0 Duration adjustable from 0 set flow temperature (see to to 300 min. coding address "FA") Fb:150 1 step ≙ 2 min 60 min. See example on page 113.
Code 2, Vitotronic 300-K Calling up coding level 2 Note ■ At coding level 2, all codes are accessible, including the codes at coding level 1. ■ Codes that have no function due to the heating system equipment level or the setting of other codes are not displayed.
Code 2, Vitotronic 300-K "General" group (cont.
Code 2, Vitotronic 300-K "General" group (cont.) Possible change 2E:2 Wireless outside temperature sensor not used. 2F:0 40:125 Never adjust Actuator runtime at plug gSA1 125 s 4A:0 Sensor aJA not fitted.
Code 2, Vitotronic 300-K 5815 091 GB Coding in the delivered condition 5b:0 Without EA1 extension 5C:0 Function output aBJ at EA1 extension: Central fault message 5d:0 Function input DE1 at EA1 extension: Without function 5E:0 Function input DE2 at EA1 extension: Without function Possible change 5b:1 With EA1 extension; recognised automatically. 5C:1 Feed pump 5C:2 Without function 5C:3 Heating circuit pump A1 is switched to low speed (reduced mode).
Code 2, Vitotronic 300-K Coding in the delivered condition 5F:0 Function input DE3 at EA1 extension: Without function 6E:50 No display correction for outside temperature 76:0 Without LON communication module 77:5 LON subscriber number 146 Possible change 5E:5 Fault message input 5E:6 Brief operation, DHW circulation pump (pushbutton function) Selection of DHW circulation pump runtime setting in coding address "12" in the "General" group 5F:1 Heating program changeover 5F:2 External demand with mi
Code 2, Vitotronic 300-K "General" group (cont.
Code 2, Vitotronic 300-K "General" group (cont.
Code 2, Vitotronic 300-K "General" group (cont.
Code 2, Vitotronic 300-K "General" group (cont.
Code 2, Vitotronic 300-K "General" group (cont.) Coding in the delivered condition 9b:70 9C:20 9F:8 Possible change 9A:7 Without function Set flow temperature for 9b:0 No default set value external demand 70 °C 9b:1 Set flow temperature adto justable from 1 to 127 °C 9b:127 With LON communication 9C:0 No monitoring module: 9C:5 Time adjustable from 5 to Monitoring LON subscrib- to 60 min.
Code 2, Vitotronic 300-K "Cascade" group (cont.) 38:0 Possible change Note Value must be lower than the lowest value of coding address "06" in group 2 of every Vitotronic 100.
Code 2, Vitotronic 300-K "Cascade" group (cont.) Coding in the delivered condition Possible change 3d:1 Output statement for con- 3d:0 No output statement densing strategy and conventional boiler stratNote egy 1 Vitotronic 300-K regulates only to conventional boiler strategy 2. 3F:0 41:31 Distribution pump will only run if there is a heat demand.
Code 2, Vitotronic 300-K "Cascade" group (cont.) Coding in the delivered condition Possible change Note A boiler or burner stage will shut down if this value is exceeded. 47:15 47:2 to 47:30 Stop differential set to 15 K. Stop differential adjustable from 2 to 30 K. Note One boiler or one burner stage will be shut down if the actual flow temperature exceeds the set flow temperature by this value.
Code 2, Vitotronic 300-K "DHW" group (cont.) Possible change Note Observe the max. permissible DHW temperature. Change over temperature controller " ". 58:0 Without auxiliary function 58:10 for DHW heating to 58:60 59:0 Cylinder heating: Set start point –2.5 K Set stop point +2.5 K For DHW heating: The set flow temperature is determined by the highest system flow temperature demand. Scan the temperature in the "Diagnosis" menu, "General" ("Common dem. temp"), see page 70.
Code 2, Vitotronic 300-K "DHW" group (cont.) Coding in the delivered condition 64:2 In party mode and after external changeover to constant operation with the standard room temperature: Constant DHW heating enabled and DHW circulation pump ON. 66:4 Input of the set DHW temperature: At the programming unit of the control unit and all installed Vitotrol 300 remote control units.
Code 2, Vitotronic 300-K "DHW" group (cont.) 70:0 71:0 68:2 to 68:10 Factor adjustable from 0.2 to 1. 1 step ≙ 0.1 69:1 to 69:9 Factor adjustable from 0.1 to 0.9. 1 step ≙ 0.1 6A:10 to 6A:255 For heat exchanger set Vitotrans 222 (240 kW): set 113 s. Runtime adjustable from 10 to 255 s. DHW circulation pump ON according to time program. DHW circulation pump 70:1 ON according to time program when DHW heating is enabled. DHW circulation pump: 71:1 ON according to time program.
Code 2, Vitotronic 300-K "Solar" group Only in conjunction with solar control module, type SM1 Coding 03:10 04:4 05:10 06:75 07:0 08:60 158 Possible change 00:2 Start temperature differento tial adjustable from 2 to 00:30 30 K 01:1 Stop temperature differento tial adjustable from 1 to 01:29 29 K 02:1 Variable speed solar circuit pump with wave packet control 02:2 Solar circuit pump speedcontrolled with PWM control Temperature differential 03:5 Temperature differential for the start of speed con- t
Code 2, Vitotronic 300-K "Solar" group (cont.) Coding in the delivered condition 09:130 Maximum collector temperature (to protect system components) 130 °C 0A:5 Temperature differential for reducing the stagnation time (reduction in solar circuit pump speed to protect system components and heat transfer medium) 5 K 0b:0 Frost protection function for solar circuit OFF Possible change 09:20 Temperature adjustable to from 20 to 200 °C.
Code 2, Vitotronic 300-K "Solar" group (cont.) Possible change 12:0 12:1 to 12:90 20:1 20:2 20:3 20:4 20:5 20:6 20:7 20:8 20:9 160 No minimum limit enabled Minimum collector temperature adjustable from 1 to 90 °C.
Code 2, Vitotronic 300-K "Solar" group (cont.
Code 2, Vitotronic 300-K "Solar" group (cont.) Coding in the delivered condition Possible change After the selected cyclical heating time for the DHW cylinder without priority has expired, the rise in collector temperature is captured during the cyclical pause time. "Heating circuit ..." group Coding A1:0 A2:2 A3:2 ! 162 Possible change A0:1 With Vitotrol 200, recognised automatically. A0:2 With Vitotrol 300 or Vitohome 300; recognised automatically.
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) Heating circuit pump ON –10 °C –9 °C –8 °C –7 °C –6 °C –5 °C –4 °C –3 °C –2 °C –1 °C 0 °C 1 °C to 14 °C Coding in the delivered condition A4:0 With frost protection OFF –8 °C –7 °C –6 °C –5 °C –4 °C –3 °C –2 °C –1 °C 0 °C 1 °C 2 °C 3 °C to 16 °C Possible change A4:1 No frost protection; this setting is only possible if code "A3:–9" has been set.
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) With heating circuit pump logic function: Heating circuit pump OFF AT > RTset + 3 K AT > RTset + 2 K AT > RTset + 1 K AT > RTset AT > RTset – 1 K AT > RTset – 9 K Coding in the delivered condition Possible change A6:36 Extended economy mode A6:5 Extended economy mode disabled to enabled. This means the A6:35 burner and heating circuit pump will stop and the mixer will be closed at a variable value, adjustable between 5 and 35 °C plus 1 °C.
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) Coding in the delivered condition (see function description on page 108).
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) Parameter address b5:... With heating circuit pump logic function: Heating circuit pump OFF Heating circuit pump ON 5 6 7 8 RTactual > RTset + 1 K RTactual > RTset RTactual > RTset – 1 K RTactual > RTset – 2 K Possible change b6:1 With quick heat-up/quick setback (see function description on page 107) b7:1 With start optimisation, max. heat-up time offset 2 h 30 min b7:2 With start optimisation, max.
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) *2 Party mode ends automatically in the "Heating and DHW" operating program when the system changes over to operation with standard room temperature. 168 5815 091 GB Coding in the delivered condition Possible change Operating program changeover to "Constant central heating with reduced room temperature" or "Standby mode" (subject to the settings of the set reduced room temperature).
Code 2, Vitotronic 300-K "Heating circuit ..." group (cont.) Coding in the delivered condition Possible change Note F2:12 Observe settings of coding addresses "5d", "5E", "5F" in the "General" group, as well as "d5" and "d8" in the "Heating circuit..." group. F9:–14 FA:20 Raising the set boiler water or flow temperature by 20 % when changing from operation with reduced room temperature to operation with standard room temperature. See example on page 113.
Schemes, Vitotronic 100, type GC1B Connection and wiring diagram 5815 091 GB Overview 170
Schemes, Vitotronic 100, type GC1B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC1B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC1B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC1B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC4B Connection and wiring diagram 5815 091 GB Service Overview 175
Schemes, Vitotronic 100, type GC4B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC4B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC4B Connection and wiring diagram (cont.
Schemes, Vitotronic 100, type GC4B Connection and wiring diagram (cont.
Schemes, Vitotronic 300-K Connection and wiring diagram 5815 091 GB Overview 180
Schemes, Vitotronic 300-K Connection and wiring diagram (cont.
Schemes, Vitotronic 300-K Connection and wiring diagram (cont.
Schemes, Vitotronic 300-K Connection and wiring diagram (cont.
Schemes, Vitotronic 300-K Connection and wiring diagram (cont.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Boiler coding card Boiler Vitocrossal 300, type CT3 Vitocrossal 200, type CM2 Vitocrossal 300, type CR3, CR3B Vitocrossal 200, type CT2 Vitocrossal 300, type CM3 Vitomax 300-LT Vitoplex 200, type SX2A Vitoplex 300, type TX3A Vitoradial 300-T Vitorond 200, type VD2, VD2A Boiler coding card Display in Identification Spare part no.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Sensors (cont.) Viessmann NTC 10 kΩ (blue ID label) Resistance in kΩ 20 1. Pull corresponding plug. 2. Check the sensor resistance and compare it with the curve. 10 8 6 4 3. In the case of severe deviation, check the installation and replace the sensor if required. 2 1 0.8 0.6 0.4 10 30 50 70 90 110 Temperature in °C Outside temperature sensor Viessmann NTC 10 kΩ 200 2.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Sensors (cont.) Viessmann NTC 20 kΩ (orange ID label) Resistance in kΩ 40 20 10 1 0.1 0 20 40 60 80 100 120 140 160 180 200 Temperature in °C 1. Pull plug aG. 2. Check the sensor resistance and compare it with the curve. 3. In the case of severe deviation, check the installation and replace the sensor if required. Plug-in adaptor for external safety equipment Part no.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Plug-in adaptor for external safety equipment (cont.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Plug-in adaptor for external safety equipment (cont.) Note A plug aBÖ must be inserted into every socket "X1", "X2", "X3" and "X7". Connecting two plug-in adaptors Separate installation instructions Make the connections in plug-in adaptor 1as described in the previous chapter. In plug-in adaptor 2, the connections can be made in any order. Rotary selector setting The rotary selector is located in the upper part of the plug-in adaptor.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Radio clock receiver (cont.) C Green LED D Red LED E Aerial Connection 2-core lead, length max. 35 m with a cross-section of 1.5 mm2. Check reception During reception, the green LED on the radio clock receiver flashes. If the red LED flashes, rotate the aerial until reception is confirmed by the flashing of the green LED.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Mixer extension kit (cont.) Changing the rotational direction (if required) 1. Pull 3-pole plug A from mixer motor, turn 180° and refit. 2. Check the rotational direction. A Open mixer Close mixer Manual mixer adjustment Lift the motor lever, unhook the mixer handle and pull plug A.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Mixer motor (cont.) For heating mixers DN 40 and 50. Y2 Y1 N 52 ?N AUTO M 1~ MAN A Mixer motor B Linked switch Open mixer Close mixer Changing the rotational direction Interchange cores at terminals "Y1" and "Y2". Checking the rotational direction The control unit relay test moves the mixer to "Open" and "Close". Manual mixer adjustment Linked switch B in "MAN" setting.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Mixer motor (cont.) Torque Runtime for 90° ∢ 5 Nm 135 s Mixer motor Part no. Z004 344 For heating mixers DN 65 and 100. 12 11 Y2 Y1 N 100% 0% 52 ?N AUTO M 1~ MAN A Mixer motor B Linked switch Open mixer Close mixer Service Changing the rotational direction Interchange cores at terminals "Y1" and "Y2". Checking the rotational direction 5815 091 GB The control unit relay test moves the mixer to "Open" and "Close".
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Mixer motor (cont.) Manual mixer adjustment Linked switch B in "MAN" setting.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K Temperature limiter for limiting the maximum temperature Immersion thermostat, part no. 7151 728 Contact thermostat, part no. 7151 729 L? N C Electromechanical temperature limiter according to the liquid expansion principle. Switches the heating circuit pump off when the set value has been exceeded. In such cases, the flow temperature reduces only slowly, i.e. it may be several hours before the system restarts again automatically.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K EA1 extension Part no.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K EA1 extension (cont.) Digital inputs DE1 to DE3 When connecting external contacts, observe the requirements of safety category II, i.e. 8.0 mm air-gap and creep paths or maintain a 2.0 mm insulation thickness against 'live' parts.
Components, Vitotronic 100, type GC1B and Vitotronic 300-K EA1 extension (cont.) Analogue input 0 – 10 V The 0 – 10 V hook-up provides an additional set flow temperature: 0 – 1 V is seen as "no set flow temperature". Note Ensure DC separation between the LV output and the earth conductor of the onsite power supply.
Parts lists Parts list Vitotronic 100, type GC1B The following information is required: ■ Serial no. (see type plate A) ■ Position number of the part (from this parts list) Standard parts are available from your local supplier. 5815 091 GB Parts 0001 Hinges 0004 Temperature controller rotary selector 0006 Temperature controller stop dial 0008 Supporting stay 0011 Safety valve with wiring 0013 Casing front with frame (with pos.
Parts lists Parts list Vitotronic 100, type GC1B (cont.
Parts lists Parts list Vitotronic 100, type GC4B The following information is required: ■ Serial no.
Parts lists Parts list Vitotronic 100, type GC4B (cont.
Parts lists Troubleshooting Vitotronic 300-K Ordering parts The following information is required: ■ Serial no. (see type plate A) ■ Position number of the part (from this parts list) 0038 0040 0042 0045 Standard parts are available from your local supplier.
Parts lists Troubleshooting Vitotronic 300-K (cont.
Specification Boiler control unit Vitotronic 100, type GC1B Mode of operation Permiss.
Specification Boiler control unit Vitotronic 100, type GC4B Mode of operation Permiss.
Specification Specification Vitotronic 300-K Rated voltage Rated frequency Rated current Power consumption Safety category IP rating Mode of operation Permiss. ambient temperature ■ During operation 0 to +40 °C Installation in living spaces or boiler rooms (standard ambient conditions) −20 to +65 °C 4 (2) A~*3 4 (2) A~*3 4 (2) A~*3 4 (2) A~*3 4 (2) A~*3 0.2 (0.
Keyword index Keyword index B Boiler, starting in boiler sequence......25 Boiler coding card ■ Identification.................................185 ■ Inserting..........................................14 Boiler control unit ■ Vitotronic 100, type GC1B......97, 205 ■ Vitotronic 100, type GC4B....100, 206 Boilers connected in parallel............101 Boilers connected in series..............101 Boiler water temperature sensor......185 Brief scan ■ Vitotronic 100..................................
Keyword index Keyword index (cont.) ERB80 function..................................98 External blocking................................40 ■ Boiler..............................................25 ■ Burner.............................................23 External changeover of multi stage/modulating burners...................................24 External demand ■ Via 0 – 10 V input...........................39 ■ Via switching contact......................
Keyword index Keyword index (cont.) Q Quick heat-up...................................107 Quick setback..................................108 R Radio clock receiver.........................189 Raising the reduced room temperature...................................................112 Reduced room temperature, raising 112 Reduced set room temperature.........65 Relay test ■ Vitotronic 100..................................61 ■ Vitotronic 300-K..............................62 Return temperature control........
5815 091 GB
7441811 Viessmann Werke GmbH&Co KG D-35107 Allendorf Telephone: +49 6452 70-0 Fax: +49 6452 70-2780 www.viessmann.com 212 7498901 7441816 Viessmann Limited Hortonwood 30, Telford Shropshire, TF1 7YP, GB Telephone: +44 1952 675000 Fax: +44 1952 675040 E-mail: info-uk@viessmann.com Subject to technical modifications. Serial No.