Operating instructions

100
Brief description
The boiler water temperature is regu-
lated by modulating the burner.
The set boiler water temperature is
determined from the following param-
eters:
Set flow temperature of heating cir-
cuit A1 (system circuit) or the heat-
ing circuits connected via LON
External demand
Cascade control of the Vitotronic 300-K
Brief description
The flow temperature is regulated by
starting or stopping the burners or by
starting/stopping individual burner
stages.
Standalone control (see page 101)
Sequential control (see page 101)
Subject to system version, we differ-
entiate between condensing strategy
(see page 102) and two conventional
boiler strategies (see page 104).
Set flow temperature
The set flow temperature is determined
from the following parameters:
Set flow temperature of heating circuit
without mixer A1 (heating circuit 1) and
heating circuits with mixer M2 (heating
circuit 2) and M3 (heating circuit 3).
Set flow temperature of additional con-
sumers.
Set DHW temperature.
External demands.
Upper control range limits:
Maximum limit of the system flow tem-
perature (coding address "37" in the
"Cascade" group).
Lower control range limits:
Minimum limit of the system flow tem-
perature (coding address "36" in the
"Cascade" group).
Function description, Vitotronic 100 and Vitotronic 300-K
Boiler control unit Vitotronic 100, type GC4B