Technical data

35
5693 973 - 05
Vitotronic 300, GW5B & MW1B Installation and Service
External Demand via 0–10V Input
Connection at input 0 – 10V at extension EA1
(see page 113).
0 - 1V no default set supply temperature
1V set value 50° F (10° C)
10V set value 212° F (100° C)
Observe coding address “1E” in the “General” group.
Installation, Vitotronic 300-K
Note: The heating system has no frost protection during
blocking. The boilers are not held at the lower boiler
water temperature.
Codes
Plug aVD
Extension EA1
Set coding address “99” in the “General” group, which
the input should influence.
Set “5D”, “5E” or “5F” in the “General” group to 3 or 4.
External Blocking via Switching Contact
Connection options:
H Plug aVD
H Extension EA1 (accessory, see page 113)
Connection
Note: ‘Live’ contacts lead to short circuits or phase
failure. The external connection must be floating.
Legend
A Floating contact
B Plug aVD of the control unit
Legend
A Floating contact
B Extension EA1
With the contact closed, the burners of all boilers will be
subject to a control shutdown.
Any connected shunt or distribution pump is stopped.
Shut-off devices are closed.