Operating instructions

117
Coding
Code 2 (cont.)
Coding in the delivered condition
Possible change
Boiler circuit/mixer circuit (cont.)
b8Ă:Ăă10
*1
With remote control and for
the heating circuit, heating
with room temperature
hook-up must be encoded:
Heat-up gradient
Start-up optimisation
10 minutes/Kelvin
b8Ă:Ăă11
to
b8
Ă:Ă255
Heat-up gradient start-up
optimisation adjustable
from 11 to 255 mins/Kelvin
b9Ă:Ăăă0
*1
With remote control and for
the heating circuit, heating
with room temperature
hook-up must be encoded:
Without learning start-up
optimisation
b9Ă:Ăăă1 With learning start-up
optimisation
C0Ă:Ăăă0
*1
Incl. remote control:
Without shutdown
optimisation
C0Ă:Ăăă1 With shutdown
optimisation (max. offset
1Ăhour)
C0Ă:Ăăă2 With shutdown
optimisation (max. offset
2Ăhours)
C1Ă:Ăăă0
*1
Incl. remote control:
Without shutdown
optimisation
C1Ă:Ăăă1
to
C1
Ă:Ăă12
With shutdown
optimisation (max. offset 10
to 120 mins.)
1 setting step ¢10Ămin
C2Ă:Ăăă0
*1
Incl. remote control:
Without learning shutdown
optimisation
C2Ă:Ăăă1 With learning shutdown
optimisation
*1
Change the code for the heating circuit without mixer A1 for boilers without lower
temperature limit or for mixer circuit, if the remote control affects that heating circuit.
5862Ă297ĂGB