Specification
Rated voltage: 230 V~
Rated frequency: 50 Hz
Rated current: 6 amp ~
Power
consumption: 5 W
Safety class: I
Protection: IP 20 D acc. to
ENĂ60529, safeguard
through appropriate
design and
installation
Function: Type 1 B acc. to
ENĂ60730Ć1
Permissible
ambient
temperature
H in operation: 0 to 40 ºC
Installation in living
accommodation and
boiler rooms
(normal ambient
conditions)
H in storage
and transport: ć20 to 65 ºC
Rated capacity of relay outputs at
230 V~ for
H Heating circuit
pump : 4 (2) A~
*1
H Circulation pump
for DHW cylinder
loading sA: 4 (2) A~
*1
H DHW circulation
pump sK: 4 (2) A~
*1
H Burner
Plug fA: 4 (2) A~
Plug :
ć two stage: 1 (0.5) A~
ć modulating: 0.1 (0.05) A~
H Central fault
message : 4 (2) A~
*1
H Total: max. 6 A~
*
1
Total max. 4 A~
5862Ă297ĂGB