Installation guide
Side Wall Vent Installation (Coaxial)
18
Component Installation Guide (continued)
Coaxial vent termination installation
Vent termination
Wall flashing (inside)
Wall flashing (outside)
Vent
system
a
in / mm
b
in / mm
60/100 4.5 / 114 27.8 / 705
80/150 5.3 / 135 29 / 735
100/150 7.3 / 185 30.8 / 782
When installing a side wall vent system
with the minimum equivalent vent
length (87º elbow and vent termination
shortened to 19”/483 mm) from boiler
back to the outside wall, a wall
thickness of at least 6”/152 mm is
required.
For walls with a thickness less than
6”/152 mm, means must be provided
to offset the boiler from the wall
(see fig. 9).
Table 7. Wall opening information
Vent system
Opening Ø
60/100 4¼”/108 mm
80/125 5¼“/133 mm
100/150 6
3
/
8
”/160 mm
Side wall vent termination installation
1. Provide side wall opening (see table
above) to install vent termination.
2. Slide vent termination
with wall
flashing
into opening (drain
openings
must be located on the
outside of the wall, pointing
downward).
3. Attach wall flashing
to inside of
wall using the screws and plugs
provided.
4. Attach wall flashing
to outside of
wall.
Total length of vent termination is
31”/787 mm. If required, the vent
termination may be shortened by max.
12”/305 mm (min. vent termination
length is 19”/483 mm).
Potential gaps between the vent-air
intake and t he surrounding construction
which may cause air, rain or flue gases
to leak into the wall or the building,
must be sealed with approved outdoor
sealant/caulking to prevent leakage of
any kind.
5368 815 v2.0 b
Fig. 8 Coaxial vent termination
for vent system 60/100, 80/125 and 100/150
b
1
2
3
6”/152 mm
Offset
Fig. 9
IMPORTANT
IMPORTANT