Installation guide

Vertical Vent Installation (Coaxial)
26
Component Installation Guide
Offset installation
(e.g. for offset venting systems)
(2 × 45º elbow)
Minimum offset of approx. 4”/100 mm: Minimum offset of approx. 5”/120 mm:
Slide two 45º elbows together Slide two 45º elbows together
and connect to coaxial vent-air intake system. and connect to coaxial vent-air intake
(vent system 80/125) system.
When the offset is larger than 4”/100 mm: When the offset is larger than 5”/120 mm:
Depending on the offset, insert extension straight Depending on the offset, insert extension
pipe (B) between the two 45º elbows. straight pipe (B) between the two 45º elbows.
(vent system 80/125) (vent system 100/150)
Table 11. Vent system 60/100 Table 12. Vent system 100/150
Offset
(in./mm)
6/
150
8/
200
9.8/
250
12/
300
13.7/
350
15.3/
390
Offset
(in./mm)
8/
200
9.8/
250
12/
300
13.7/
350
15.3/
390
Extension
(in./mm)
Height
(in./mm)
6.3/
161
9.8/
249
9.1/
232
11.8/
299
11.9/
303
13.7/
349
14.7/
373
15.7/
399
17.5/
444
17.7/
449
19.7/
501
19.3/
489
Extension
(in./mm)
Height
(in./mm)
6.7/
170
12.6/
320
8.5/
215
14.2/
360
11.2/
285
16.1/
410
14/
355
18.1/
460
16.1/
410
19.7/
500
Table 13. Vent system 80/125
Offset
(in./mm)
6/
150
8/
200
9.8/
250
12/
300
13.7/
350
15.3/
390
Extension
(in./mm)
Height
(in./mm)
5/
122
10.6/
270
7.6/
193
13/
330
10.4/
264
15/
380
15.1/
384
17/
430
16/
405
19/
480
19.7/
500
21.5/
547
5368 815 v2.0 b