Operating instructions
For further details regarding faults,
see page 69.
Checking the static and supply pressure
Danger
CO build-up as a result of an incorrect burner setup can have serious
health implications.
Carry out a CO test prior to and after work on gas equipment.
Operation with LPG
Flush the LPG tank twice during commissioning/replacement. Thoroughly vent
the tank and gas supply lines after flushing.
1. Close the gas shut-off valve.
2. Undo the screw inside test connec-
tor "IN" A on the gas train, but do
not remove, then connect the pres-
sure gauge.
3. Open the gas shut-off valve.
4. Measure the static pressure and
record it in the service report.
Set value: max. 57.5 mbar.
5. Start the boiler.
Note
During commissioning, the boiler
can enter a fault state because of
airlocks in the gas pipe. After
approx. 5 s, press "E RESET" to
reset the burner.
Further details regarding the individual steps (cont.)
14
Commissioning, inspection, maintenance
5692 672 GB