Operating instructions
Checking and adjusting the ignition and ionisation electro-
des
A Ignition electrodes B Ionisation electrode
1. Check the electrodes for wear and
contamination.
2. Clean the electrodes with a small
brush (not with a wire brush) or
emery paper.
3. Check the electrode gaps. If the
gaps are not as specified or the
electrodes are damaged, replace
and align the electrodes together
with new gaskets. Tighten the elec-
trode fixing screws with 2.5 Nm.
Cleaning the heating surfaces and installing the burner
!
Please note
Scratches on parts that are in contact with flue gas can lead to corrosion.
Never use brushes to clean the heat exchanger.
Further details regarding the individual steps (cont.)
20
Commissioning, inspection, maintenance
5692 672 GB