Operating instructions
System version 2
One heating circuit without mixer A1 and one heating circuit with mixer M2
(with/without DHW heating)
Note
The volume flow of the heating circuit without mixer must be at least 30%
greater than the volume flow of the heating circuit with mixer.
1 Vitodens 200-W
2 Outside temperature sensor
3 DHW cylinder
4 Cylinder temperature sensor
5 Heating circuit without mixer A1
6 Heating circuit with mixer M2
7 Temperature limiter for limiting the
max. temp. of underfloor heating
systems
8 Flow temperature sensor M2
9 Heating circuit pump M2
qP Extension kit for one heating cir-
cuit with mixer M2
Required coding Address
Operation with LPG 82:1
System with only one heating circuit with mixer
&
with DHW heating 00:4
&
without DHW heating 00:3
Further details regarding the individual steps (cont.)
26
Commissioning, inspection, maintenance