Operating instructions

Coding in the delivered condition Possible change
58:0 Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW temperature, adjus-
table from 10 to 60 °C
(observe coding ad-
dresses "56" and "63")
59:0 Cylinder heating:
Starting point -2.5 K
Stopping point +2.5 K
59:1
to
59:10
Starting point adjustable
from 1 to 10 K below the
set value
5b:0 DHW cylinder directly
connected to the boiler
5b:1 DHW cylinder connected
downstream of the low
loss header
60:20 During DHW heating,
the boiler water tem-
perature is max. 20 K
higher than the set
DHW temperature
60:5
to
60:25
The difference between
the boiler water tempera-
ture and the set DHW
temperature is adjustable
from 5 to 25 K
62:2 Circulation pump with
2 min run-on time after
cylinder heating
62:0 Circulation pump without
run-on
62:1
to
62:15
Run-on time adjustable
from 1 to 15 min
63:0 Without auxiliary func-
tion for DHW heating
(only for constant tem-
perature control units)
63:1 Auxiliary function: 1 x
daily
63:2
to
63:14
Every 2 days to every 14
days
63:15 2 x daily
65:... Information regarding
the type of diverter
valve (not adjustable)
65:0 Without diverter valve
65:1 Diverter valve by
Viessmann
65:2 Diverter valve by Wilo
65:3 Diverter valve by Grund-
fos
67:40 With the Vitosolic: Third
set DHW temperature =
40 °C
67:0 Without third set DHW
temperature
67:1
to
67:60
Third set DHW tempera-
ture adjustable from 1 to
60 °C (subject to the set-
ting of coding address
"56")
Code 2 (cont.)
46
Coding
5692 672 GB