Operating instructions
Coding in the delivered condition Possible change
6F:... Maximum output for
DHW heating in %; de-
faulted by the boiler
coding card
6F:0
to
6F:100
Max. output during DHW
heating adjustable from 0
to 100 %
71:0 DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
71:1 "OFF" during DHW heat-
ing to the first set value
71:2 "ON" during DHW heat-
ing to the first set value
72:0 DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
72:1 "OFF" during DHW heat-
ing to the second set
value
72:2 "ON" during DHW heat-
ing to the second set
value
73:0 DHW circulation pump:
"ON" in accordance
with the time program
(only for weather-com-
pensated control units)
73:1
to
73:6
during the time program
"ON" 1x/h for 5 min
"ON" up to 6x/h for 5 min
73:7 permanently "ON"
General
76:0 Without LON communi-
cation module (only for
weather-compensated
control units)
76:1 With LON communication
module; automatic recog-
nition
77 :1 LON subscriber number
(only for weather-com-
pensated control units)
77 :2
to
77 :99
LON subscriber number,
adjustable from 1 to 99:
1 - 4 = Boiler
5 = Cascade
10 - 98 = Vitotronic 200-H
99 = Vitocom
Note
Allocate each number
only once.
79:1 With LON communica-
tion module: Control
unit is fault manager
(only for weather-com-
pensated control units)
79:0 Control unit is not fault
manager
Code 2 (cont.)
47
Coding
5692 672 GB