Operating instructions
Coding in the delivered condition Possible change
E1:1 With remote control:
The set day tempera-
ture is adjustable at the
remote control unit from
10 to 30 °C (only for
weather-compensated
control units)
E1:0 Set day temperature ad-
justable from 3 to 23 °C
E1:2 Set day temperature ad-
justable from 17 to 37 °C
E2:50 With remote control: No
display correction for
the actual room tem-
perature (only for
weather-compensated
control units)
E2:0
to
E2:49
Display correction -5 K
to
Display correction -0.1 K
E2:51
to
E2:99
Display correction +0.1 K
to
Display correction +4.9 K
F1:0 Screed drying function
disabled (only for
weather-compensated
control units).
F1:1
to
F1:6
Screed drying function
adjustable in accordance
with 6 optional tempera-
ture/time profiles (see
page 100)
F1:15 Constant flow tempera-
ture 20 °C
F2:8 Time limit for party
mode or external heat-
ing program change-
over via key: 8 hours
(only for weather-com-
pensated control units)
*
1
F2:0 No time limit for party
mode
F2:1
to
F2:12
Time limit adjustable from
1 to 12 hours
*
1
F5:12 Run-on time of the inter-
nal circulation pump in
heating mode 12 min
(only for constant tem-
perature control units)
F5:0 No run-on time for the in-
ternal circulation pump
F5:1
to
F5:20
Run-on time of the inter-
nal circulation pump ad-
justable from 1 to 20 min
Code 2 (cont.)
56
Coding
5692 672 GB
*1
Party mode ends automatically in the "Heating and DHW" program, when the system
changes over to operation with standard room temperature.