Operating instructions

Coding in the delivered condition Possible change
F6:25 In the "DHW only" oper-
ating mode, the internal
circulation pump is per-
manently ON (only for
constant temperature
control units)
F6:0 In the "DHW only" operat-
ing mode, the internal cir-
culation pump is
permanently OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the internal cir-
culation pump will be
started for 10 min respec-
tively 1 to 24 times per
day.
F7:25 In "Standby mode", the
internal circulation
pump is permanently
ON (only for constant
temperature control
units)
F7:0 In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
to
F7:24
In "Standby mode", the
internal circulation pump
in operating mode will be
started for 10 min respec-
tively 1 to 24 times per
day.
F8:-5 Temperature limit for
terminating the reduced
mode -5 ºC, see exam-
ple on page 102.
Observe the setting of
coding address "A3".
(only for weather-com-
pensated control units)
F8:+10
to
F8:-60
Temperature limit adjus-
table from
+10 to -60 °C
F8:-61 Function disabled
F9:-14 Temperature limit for
raising the reduced set
room temp. -14 ºC, see
example on page 102.
(only for weather-com-
pensated control units)
F9:+10
to
F9:-60
Temperature limit for rais-
ing the set room tempera-
ture to the value selected
for standard mode adjus-
table from
+10 to -60 °C
Code 2 (cont.)
57
Coding
5692 672 GB