Operating instructions
Fault
code
on the
display
Const. weath.-
comp.
System char-
acteristics
Cause Measures
b5 X X Control mode
as per deliv-
ered condition
Internal fault Replace the con-
trol unit.
b7 X X Burner
blocked
Boiler coding
card miss-
ing, faulty or
incorrect
boiler coding
card
Plug in boiler cod-
ing card or re-
place it, if faulty.
b8 X X Burner
blocked
Flue gas
temperature
sensor lead
broken
Check the flue
gas temperature
sensor (see
page 85).
bA X Mixer M2 reg-
ulates to a
flow tempera-
ture of 20 °C.
Communica-
tion fault –
extension kit
for heating
circuit M2
Check the exten-
sion kit connec-
tions and coding.
Start the exten-
sion kit.
bC X Control mode
without remote
control
Communica-
tion fault –
Vitotrol re-
mote control,
heating cir-
cuit A1
Check connec-
tions, cable, cod-
ing address "A0"
and remote con-
trol DIP switches
(see page 104).
bd X Control mode
without remote
control
Communica-
tion fault,
Vitotrol re-
mote control,
heating cir-
cuit M2
Check connec-
tions, cable, cod-
ing address "A0"
and remote con-
trol DIP switches
(see page 104).
bE X Control mode Vitotrol re-
mote control
incorrectly
programmed
Check remote
control DIP switch
settings (see
page 104).
bF X Control mode Incorrect
LON com-
munication
module
Replace the LON
communication
module.
Fault codes (cont.)
73
Troubleshooting
5692 672 GB