Technical data

Control Technology
35
Outdoor Reset Programming Unit
(continued)
Connecting the boiler control to a LON system
(continued)
Performing participant check
Conditions:
A Consecutive number in the
participant list
B Participant number
H The control unit must be
programmed
as fault manager (code ”79:1”)
H The LON participant number must
be programmed in all control units
(see table on previous page)
H The LON participant list in the fault
manager must be up-to-date
(see table on page 33)
1. Press w + simultaneously
for approx. 2 sec. Participant check
is initiated.
2. Press / for required
participant.
3. Press . Check is
enabled.”Check” flashes until its
completion. The display and all key
illuminations for the selected
participant flash for approx. 60 sec.
4. Check OK is displayed during
communication between both
devices.
or
Check not OK is displayed if
there is no communication
between both devices. Check the
LON connection.
5. Repeat steps 2 and 3 to check
other participants.
6. Press w + simultaneously
for approx. 1 sec. The participant
check is completed.
Instructing the system user
The system installer must hand the operating instructions to the system user
and instruct him/her in the operation of the system.