Technical data

Coding
48
Coding Level 2
(continued)
Overview of coding addresses
(continued)
Coding (factory default setting) Possible change
Boiler circuit, mixing valve circuit
A9:7 With pump stop function: Heating circuit
p
u
m
p
O
F
F
i
f
t
h
e
s
e
t
p
o
i
n
t
c
h
a
n
g
e
s
A9:0 Without pump stop function
p
u
m
p
O
F
F
i
f
t
h
e
s
e
t
p
o
i
n
t
c
h
a
n
g
e
s
through a change in operating mode or
through a change in the room
temperature setpoint
A9:1
to
A9:15
With pump stop function; adjustable from
1 to 15
b0:0
*1
With remote control:
Heating mode / reduced mode:
With outdoor reset
b0:1 Heating mode: With outdoor reset
Reduced mode: With room temperature
feedback
W
i
t
h
o
u
t
d
o
o
r
r
e
s
e
t
b0:2 Heating mode: With room temperature
feedback
Reduced mode: With outdoor reset
b0:3 Heating mode / reduced mode:
With room temperature feedback
b1:0 Do not adjust
b2:8
*1
With remote control unit and for heating
c
i
r
c
u
i
t
,
o
p
e
r
a
t
i
o
n
w
i
t
h
r
o
o
m
t
e
m
p
e
r
a
t
u
r
e
b2:0 No room influence
b
2
:
8
W
i
t
h
r
e
m
o
t
e
c
o
n
t
r
o
l
u
n
i
t
a
n
d
f
o
r
h
e
a
t
i
n
g
circuit, operation with room temperature
feedback must be programmed:
Room influencing factor 8
b2:1
to
b2:31
Room influence factor adjustable from 1 to 31
b3:0 Do not adjust
b5: 0
*1
With remote control:
Without room temperature dependent
heating circuit pump logic function
Note: T=Temperature difference
b5:1 Heating circuit pump
ON at RT
actual
> RT
set
+ T
OFF, at RT
actual
< RT
set
+ T
T for ON T for OFF
4K / 7F 5K / 9F
N
o
t
e
:
T
=
T
e
m
p
e
r
a
t
u
r
e
d
i
f
f
e
r
e
n
c
e
b5:2 3K / 5F 4K / 7F
b5:3 2K / 4F 3K / 5F
b5:4 1K / 2F 2K / 4F
b5:5 0K / 0F 1K / 2F
b5:6 -1K / -2F 0K / 0F
b5:7 -2K / -4F -1K / -2F
b5:8 -3K / -5F -2K / -4F
C5:20 Electronic minimum supply temperature
limit 68°F / 20°C
C5:1
to
C5:127
Minimum temperature limit adjustable from
34 to 261°F / 1 to 127°C (limited by the
boiler coding card)
C6:74 Electronic maximum supply temperature
limit 165°F / 74°C
C6:10
to
C6:127
Maximum temperature limit adjustable from
50 to 261°F / 10 to 127°C (limited by the
boiler coding card)
d3:14 Heating curve slope = 1.4 d3:2
to
d3:35
Heating curve slope adjustable from 0.2 to 3.5
(see page 31).
d4:0 Heating curve shift = 0 d4:-13
to
d4:40
Heating curve shift adjustable from -13 to 40 K
(see page 31)
*1
Change coding for heating circuit without mixing valve A1 only for boilers without lower temperature limit
for heating circuit with mixing valve M2 only, if remote control unit affects this heating circuit.
5418 911 v1.6