Technical data

Additional Information
66
Control Functions
(continued)
Reducing the heat-up time
During the transition from operation with reduced room temperature to
operation with standard room temperature, the boiler water or supply
temperature will be raised in accordance with the selected heating curve. The
boiler water or supply temperature can be automatically increased. The value and
duration of the additional increase of the set boiler water temperature or supply
temperature can be adjusted in coding addresses ”FA” and ”Fb”.
Remote control (Vitotrol 300) DIP switch settings
The DIP switches are located on the PCB in the top part of the housing.
Remote control DIP switch setting
The remote control affects the heating
circuit without mixing valve (A1)
2
1
ON
3 4
The remote control affects the heating
circuit with mixing valve (M2)
2
1
ON
3 4
When connecting a separate room
temperature sensor, set DIP switch ”3”
to ”ON”.
2
1
ON
3 4
5418 911 v1.6
10
0
20
3030
40
50
60
6
00
7
00
8
00
9
00
Boiler / Supply Water
Setpoint Temperature in
Time in hr.
A
B
C
D
Fig. 28 Example (using factory default settings)
A Start of operation with standard room
temperature
B Boiler water / supply temperature
based on selected heating curve
C Boiler water / supply temperature
based on coding address ”FA”:
50°C + 20 % = 60°C
D Duration of operation with raised
boiler water / supply temperature
based on coding address ”Fb”: 60 min.
°C
Refer to Operating Instructions
Vitotrol 300 Remote Control