Operating instructions

Setting and test values Set value Initial
start-up
Mainte-
nance/ser-
vice
Date:
By:
Static pressure mbar max.
57.5 mbar
Supply pressure (flow
pressure)
= for natural gas E mbar 17.4-
57.5 mbar
= for natural gas LL mbar 17.4-
57.5 mbar
= for LPG mbar 42.5-
57.5 mbar
Tick gas type
Carbon dioxide content
CO
2
&
at the lower rated output %vol.
&
at the upper rated out-
put
%vol.
Oxygen content O
2
&
at the lower rated output %vol.
&
at the upper rated out-
put
%vol.
Carbon monoxide con-
tent CO
&
at the lower rated output ppm
&
at the upper rated out-
put
ppm
Ionisation current µA min. 2 µA
Commissioning/service reports
117
Commissioning/service reports
5692 619 GB