Operating instructions

Yes
Gas combination
valve opens
No
Fault F4 Check the gas
combination valve
(control voltage
230 V); check the
gassupplypres-
sure
Yes
Ionisation cur-
rent builds
(higher tha n
2ยตA)
Symbol A
No
Fault F4 Check ionisatio n
current, check
electrode adjust-
ment and gas
pipe for airlocks.
Yes
Burner starts No Stops below set
boiler water tem-
perature and re-
starts immedi-
ately
Check flue gas
system sound-
ness (flue gas re-
circulation) ,
check gas flow
pressure
For further details regarding faults, see page 69.
Checking the static and supply pressure
Danger
CO build-up as a result of incorrect burner setting can have serious
health implications.
Carry out a CO test prior to, and after, work on gas equipment.
Operation with LPG (only 26 kW)
Flush the LPG tank twi ce during commissionin g/replacement. Tho roughly vent
the tank and gas lin es after flushin g.