Operating instructions

Checking the condensate drain and cleaning the siphon
1. Check that the condensate can
freely drain at siphon A.
2. Remov e the retaining c lip and the
siphon.
3. Clea n the siphon.
4. Fit the siphon and secure with the
retaining clip.
Testing the anode earth current with an anode tester
Note
We recommend that the ma gnesium anode f unction is checke d annually. This
function test can be carried out without interrupting operation by measuring the
earth current with an anode tester.
A Cover
B Earth cable
C Push-on tab
1. Remove cover A.
2. Pull earth cable B from push-on
tab C.
3. Connect the tester (up to 5 mA) in
series between push- on tab C
and earth cable B.
&
The anode is OK if the indicated
current is > 0.3 mA .
&
Visually inspect the anode if the
current mea sures < 0.3 mA or if
there is no current at all (see
page 22).
Further details regarding the individual steps (cont.)
21
Initial start-up, inspection, maintenance
5692 619 GB