Cleaning the DHW cylinder
Note
DIN 1988 requires a visual inspection and (if necessary) cleaning every two
years after the cylinder has been taken into use and thereafter according to
requirements.
1. Drain the DHW cylinder.
2. Remov e flange lid A.
3. Disconnect the cylinder from the
pipework to prevent c ontaminants
entering the pipe system.
4. Remove loose deposits with a high
pressure cleaner.
!
Please note
Only use plastic utensils for
cleaning the insi de of the
cylinder.
5. Use a che mical cleaning age nt to
remove hard deposits that cannot
be removed by a hi gh pressure
cleaner.
!
Please note
Never use hydr ochloric
cleaning agents.
6. Thoroughly flush the DHW cylinder
after cleaning.
Checking and replacing the magnesium anode (if required)
Check the magnesium anode. We recommend you change the magnesium
anodeifithasbeenreduceddownto10to15m.
Further details regarding the individual steps (cont.)