Operating instructions

Flue gas emissions test
The Vitodens 333 is set up in the factory for natural gas E and can, with the aid
of a conversion kit, be conve rted to natural gas LL or LPG P (on ly 26 kW).
During commissioning o r maintenance, check the CO
2 leve l at the flue outlet .
Note
The MatriX burner of the Vitodens 333 is preset for the entire gas group. There-
fore, the burner re quires no furthe r setting or adjustment.
Subject to the Wobbe index, the CO
2 content fluctuates between
&
6.6 to 10.0% for natural gas E
&
7.0 to 10.0% for natural gas LL
&
8.5 to 10.5% for LPG P (only 26 kW)
Compare the actual CO
2 value with the above CO2 value range s for the indiv i-
dual gas groups (check the gas group with your mains gas or LPG supplier).
If the actual CO
2 valu e deviates by mor e than 1% for na tural gas or 0.5% f or
LPG (only 26 kW), proceed as follows:
&
Check that the cor rect gas restrictor h as been installed.
&
Check the balanced flue system for soundness, see page 16.
Maintain limit s to EN 483 and EN 297 (CO conte nt < 1000 ppm).
1. Connect a flue gas analyser at the
flue gas port A ontheflueoutlet.
2. Open the ga s shut-off valve, start
the boiler and create a heat
demand.
3. Select the lower rated output.
Constant temperature control
unit:
Press K + d simultaneously:
"1"isshown.
Weath er compensated control
unit:
Press K + d simultaneously:
"Relay test"and
then "Base load"is
shown.
4. Check the CO
2 content. If the v alue
lies outside the above range, take
themeasureslistedonpage24.
Further details regarding the individual steps (cont.)
24
Initial start-up, inspection, maintenance
5692 619 GB