Operating instructions
Coding in the delivered condition Possible change
Slope A1/M2
d3:14 Heating curve slope =
1.4 (only for wea ther-
compensated control
units)
d3:2
to
d3:35
Heating curve sl ope ad-
justable f rom 0.2 to 3.5
(see page 32)
Level A1/M2
d4:0 Heating curve slope = 0
(only for weather-co m-
pensated control units)
d4:–13
to
d4:40
Heating curve level ad-
justable f rom – 13 to 40
(see page 32)
Code 2
Calling up code 2
Note
&
On weather-compensated control
units, codes are displayed as plain
text.
&
Codes, which are irrelevant (due to
the system equipment level or the
setting of other co des) will not be
displayed.
Press the follo wing keys:
1. L + G simultaneously for
approx. 2s.
2. d to confirm.
3. a/b for the require d coding
address; the address
flashes.
4. d to confirm; the value
flashes.
5. a/b for the selected v alue.
6. d to confirm; the display
briefly shows
"accepted"(for
weather-compensated
control units); the
address flashes again.
7. a/b for the selection of
further addresses.
8. L + G simultaneously for
approx. 1 s to terminate
code 2.
Overall summary
Thecodingaddressesaregroupedaccordingtothefollowingfunction areas.
The respective funct ion area is shown o n the display.
Code 1 (cont.)
41
Coding
5692 619 GB