Operating instructions
Coding in the delivered condition Possible change
Domestic hot water
56:0 Set DHW temperature
adjustable from 10 to
60 °C
56:1 Set DHW temperature
adjustable from 10 to
above 60 °C
Note
Maximum value subject
to boiler coding card
Observe the max. per-
missible DHW tempera-
ture
58:0 Without auxiliary func-
tion for DHW heating
58:10
to
58:60
Input of a second set
DHW value, adjus table
from 10 to 60 °C (observe
the coding addre sses
"56" and "63" )
63:0 No default interval for
auxiliary function for
DHW heating (only for
constant temper ature
control units)
63:1 Auxiliary function for
DHW heating, 1 x daily
63:2
to
63:14
Every 2 days to ev ery 14
days
63:15 2 x daily
65:... Information regarding
the type of diverter
valve; do not a djust.
65:0 Without diverter valve
65:1 Viessmann diverter valve
65:2 Wilo diverter valve
65:3 Grunfos diverter valve
67:40 With the Vitosolic:
third set DHW tempera-
ture 40 °C
67:0 Without third set DHW
temperature
67:1
to
67:60
Third set DHW tempera-
ture adjus table from 1 t o
60 °C (subject to the set-
ting of coding address
"56")
6C:100 Set speed of the inter-
nal cylinder primary
pump 100 %
6C:0
to
6C:100
Set speed adjustable
from0to100%
6F:... Maximum output for
DHW heating in %; de-
faulted by the boiler
coding card
6F:0
to
6F:100
Max. output during DHW
heating ad justable from
min. output to 100 %
Code 2 (cont.)
46
Coding
5692 619 GB