Operating instructions

Coding in the delivered condition Possible change
A9:7 With pump idle period:
Heating circuit pump
"OFF" when the set
value chang es through
achangeinoperating
mode or through a
change in the set r oom
temperature (only for
weather-compensated
control units)
A9:0 Without p ump idle period
A9:1
to
A9:15
With pump idle period,
adjustable from 1 to 15
b0:0 With remote control:
Heating mode/r educed
mode: weather-co m-
pensated (only for
weather-compensated
control units; cha nge
the coding only fo r the
heating ci rcuit with
mixer M2)
b0:1 Heating mode: weather-
compensated
Reduced mode: wit h
room temperature hook-
up
b0:2 Heating mode: with room
temperature hook-up
Reduced mode: wea ther-
compensated
b0:3 Heating mode/reduced
mode: with r oom tem-
perature hook -up
b2:8 With remote control unit
andfortheheatingcir-
cuit, heating with room
temperature hook-up
must be encoded:
Room influence factor 8
(only for weather-co m-
pensated control units;
change the codin g only
for the heating circuit
with mixer M2)
b2:0 Without room influence
b2:1
to
b2:64
Room influence factor
adjustable from 1 to 64
b5:0 With remote control: No
room temperatu re-de-
pendent heating circuit
pump logic fun ction
(only for weather-co m-
pensated control units;
change the codin g only
for the heating circuit
with mixer M2)
b5:1
to
b5:8
Heating circuit pump
logic function, see the fol-
lowing table:
Code 2 (cont.)
54
Coding