Operating instructions

Coding in the delivered condition Possible change
E1:1 With remote control:
The set day temp era-
ture is adjustable at the
remote control unit from
10 to 30 °C ( only for
weather-compensated
control units)
E1:0 Set day temperature ad-
justablefrom3to2C
E1:2 Set day temperature ad-
justable f rom 17 to 37 °C
E2:50 Withremotecontrol:No
display corr ection for
the actual room tem-
perature (only for
weather-compensated
control units)
E2:0
to
E2:49
Display correction 5K
to
display correcti on -0.1 K
E2:51
to
E2:99
Display correction +0.1 K
to
display correcti on +4.9 K
E5:0 Without varia ble speed
external heating circuit
pump (only for weather-
compensated control
units)
E5:1 With external variable
speed heating circuit
pump (autom atic recogni-
tion)
E6:100 Maximum spee d of the
external variab le speed
heating ci rcuit pump:
100 % of the spe ed in
standard mode (only for
weather-compensated
control units)
E6:0
to
E6:100
Maximum speed adjusta-
blefrom0to100%
E7:30 Minimum speed of the
external variab le speed
heating ci rcuit pump:
30 % of the maximum
speed (only for weath-
er-compensated control
units)
E7:0
to
E7:100
Minimum speed adjusta-
blefrom0to100%of
max. speed
E8:1 Minimum speed in op-
eration with r educed
room temperature sub-
ject to the setting of
coding addr ess "E9"
(only for weather-co m-
pensated control units)
E8:0 Speed subject to the set-
ting in coding address
"E7"
Code 2 (cont.)
56
Coding
5692 619 GB