Operating instructions

Coding in the delivered condition Possible change
E9:45 Speed of the ex ternal
variable speed heating
circuit pump: 45 % of
the maximum s peed in
reduced tempe rature
mode (only for weather-
compensated control
units)
E9:0
to
E9:100
Speed adjustable from 0
to 100 % of maximum
speedduringoperation
with reduced room tem -
perature
F2:8 Time limit for party
mode8horexternal
heating program chan-
geover via th e keyboard
(only for weather-co m-
pensated control units)
*
1
F2:0 No time limit for party
mode
*
1
F2:1
to
F2:12
Time limit adjustable from
1to12h
*
1
F5:12 Run-ontimeoftheinter-
nal circula tion pump in
heating mo de (only for
constant temper ature
control units)
F5:0 No run-on time of the in-
ternal circulation pump
F5:1
to
F5:20
Run-on time of the inter-
nal circula tion pump ad-
justablefrom1to20min
F6:25 In the "DHW only" oper-
ating mode, the internal
circulation pump i s per-
manently ON (onl y for
weather-compensated
control units)
F6:0 In the "DHW only" operat-
ing mode, the i nternal cir -
culation pump is
permanentl y OFF
F6:1
to
F6:24
In the "DHW only" operat-
ing mode, the i nternal cir -
culation pump will be
started1to24timesper
day for 10 min respec-
tively.
F7:25 In the "Standby" operat-
ing mode, the i nternal
circulation pump i s per-
manently ON (onl y for
constant temper ature
control units)
F7:0 In "Standby mode", the
internal circulation pump
is permanently OFF
F7:1
to
F7:24
In the "Standby" mode ,
the internal ci rculation
pump in operating mode
willbestarted1to24
times per day for 10 min
respectively.
Code 2 (cont.)
57
Coding
5692 619 GB
*1
Party m ode ends automatically in the " Heating and DHW" program, when the system
changes over to operation wi th standard room temperature.