Operating instructions
Coding in the delivered condition Possible change
Heating circuit M2
F1:0 Screed drying function
disabled (only for
weather-compensated
control units)
F1:1
to
F1:5
Screed drying function
adjustab le in accordan ce
with five optional tem-
perature/time profiles
(see page 101)
Note
Observe the screed sup-
plier's instructions.
Observe DIN 4725–2.
Thereporttobeprovided
by the heating contractor
must contain the follow-
ing heat-up details:
&
Heat-up data with
respective flow tem-
peratures
&
Max. flow temperat ure
achieved
&
Operating condi tion
and outside tempera-
ture during hand over
The function continues
after a power fai lure or
after the cont rol unit has
been switched OFF.
Heating program "Heat-
ing and DHW" will be
started after the screed
function has been termi-
nated or if the address is
manually set to 0.
F1:6
to
F1:15
Constant flow tempera-
ture 20 °C
Code 2 (cont.)
59
Coding
5692 619 GB